백연 저감을 위한 열교환 시스템의 배기 열전달 특성에 관한 연구
Study on Exhaust Air Heat Transfer Characteristics of Heat Exchange System for White Smoke Reduction
0
조회
0
다운로드
9
인용
0
참고문헌
키워드
초록
In this study, effects of reducing white smoke at a heat exchange system for white smoke reduction were studied in the winter season. For this purpose, the heat transfer processes on the exhaust air were investigated by Solidworks. Five wave heat exchangers of air-to-air and air-to-water type were applied for the exhaust air heat recovery. The analytical condition of the exhaust air was fixed and the computational analysis was performed according to the change of SA(supply air) inlet velocities. In order to evaluate the performance of the heat exchange system for white smoke reduction, W(water)/SA recovered capacities and the temperature/absolute humidity reduction rate were calculated. As SA inlet velocity increased, the exit temperature andabsolute humidity of the mixing zone were reduced by up to about 40℃ and 0.12kg/kg respectively. Also, W/SA recovered capacities increased linearly up to about 35%.
Abstract
In this study, effects of reducing white smoke at a heat exchange system for white smoke reduction were studied in the winter season. For this purpose, the heat transfer processes on the exhaust air were investigated by Solidworks. Five wave heat exchangers of air-to-air and air-to-water type were applied for the exhaust air heat recovery. The analytical condition of the exhaust air was fixed and the computational analysis was performed according to the change of SA(supply air) inlet velocities. In order to evaluate the performance of the heat exchange system for white smoke reduction, W(water)/SA recovered capacities and the temperature/absolute humidity reduction rate were calculated. As SA inlet velocity increased, the exit temperature andabsolute humidity of the mixing zone were reduced by up to about 40℃ and 0.12kg/kg respectively. Also, W/SA recovered capacities increased linearly up to about 35%.
참고문헌 (8)
- 왕쩐후안, "파형 열교환기의 열전달 및 유동특성에 관한 전산해석 연구", 한국기계기술학회지, 19(4), pp.452~457 (2017), 한국기계기술학회[DOI]
- 왕쩐후안, "백연저감 시스템용 Pilot 파형 열교환기 열전달 특성에 대한 실험적 연구", 한국기계기술학회지, 19(5), pp.632~637 (2017), 한국기계기술학회[DOI]
- Cho, G. H., "Performance test of pilot white smoke reduction system", Korea Academia-Industrial cooperation Society Spring Conference paper, pp.772~774 (2017)
- Wang, Z. H, "Numerical study on flow characteristics for white smoke reduction of heat exchanger system", Korea Academia-Industrial cooperation Society Spring Conference paper, pp.775~777 (2017)
- 손준, "균일유동에서 백연저감용 전열판 형태에 대한 열유동 특성", 한국산학기술학회논문지, 17(1), pp.591~596 (2016), 한국산학기술학회[DOI]
- 유성연, "플라스틱 판형 열교환기의 성능에 관한 실험적 연구", 설비공학 논문집, 17(2), pp.117~124 (2005), 대한설비공학회
- Kim, D. H., "Analysis on operating characteristics of white smoke reduction system", Korea Academia-Industrial cooperation Society Spring Conference paper, pp.781~783 (2017)