백연저감 열교환 시스템의 형상 변화에 따른 혼합부의 유동특성 연구
Study on Flow Characteristics of Mixer by Shape Change of White Heat Reduction Heat Exchange System
1
조회
0
다운로드
0
인용
0
참고문헌
키워드
초록
In this study, the temperature, the absolute humidity, and the turbulent flow characteristics of exhaust air and supply air in the mixer were studied while changing the shape of the mixer of the white smoke reducing heat exchange system. Using Solidworks, the mixer of the white smoke reduction heat exchange system was created by 3-D model. Also, the mixed flow of supply air and exhaust air inside the mixer under the uniform inlet conditions was computed, using the solidworks flow simulation. Two types of improvement models were selected by using a perforated plate and a guide vane as a turbulent mixing flow control method of the mixer. The mean temperature and mean absolute humidity of the mixture were greatly decreased according to the internal shapes of Case 1, 2, and 3. The temperature difference between the inlet and outlet of the mixer Case 3 was 26℃. The exit temperature and absolute humidity reduction rates of Case 3 were 26.2% and 48.1%, respectively, compared with Case 1.
Abstract
In this study, the temperature, the absolute humidity, and the turbulent flow characteristics of exhaust air and supply air in the mixer were studied while changing the shape of the mixer of the white smoke reducing heat exchange system. Using Solidworks, the mixer of the white smoke reduction heat exchange system was created by 3-D model. Also, the mixed flow of supply air and exhaust air inside the mixer under the uniform inlet conditions was computed, using the solidworks flow simulation. Two types of improvement models were selected by using a perforated plate and a guide vane as a turbulent mixing flow control method of the mixer. The mean temperature and mean absolute humidity of the mixture were greatly decreased according to the internal shapes of Case 1, 2, and 3. The temperature difference between the inlet and outlet of the mixer Case 3 was 26℃. The exit temperature and absolute humidity reduction rates of Case 3 were 26.2% and 48.1%, respectively, compared with Case 1.
참고문헌 (8)
- 이중섭, "8kW급 디젤발전기 소음기 내부 유동에 관한 수치해석", 한국기계가공학회지, 17(3), pp.45~50 (2018), 한국기계가공학회[DOI]
- 최용석, "병렬 마이크로 채널 형상에 따른 CFD 유동해석", 수산해양교육연구, 25(5), pp.1102~1109 (2013), 한국수산해양교육학회[DOI]
- Y. M. Kim, "Numerical Investigation of Flows in a 90-Degree T-Branch of Square Cross-Section", Journal of the Korean Society for Aeronautical &Space Sciences, 26(1), pp.52~63 (1998)
- 김승일, "T-분지관이 부착된 벤튜리관의 유동특성과 응축수 유입에 대한 수치해석 연구", 한국산업융합학회논문집, 22(2), pp.173~181 (2019), 한국산업융합학회[DOI]
- 김석범, "혼합배관 내의 열 경계층 이동으로 인한 고주기 온도요동에 관한 연구", 한국유체기계학회 논문집, 10(5), pp.9~19 (2007), 한국유체기계학회
- K. H. Kim, "A Characteristic Study on Velocity Distribution by Location and Uniformity Index according to Exit Straight Length in a 180° Circular Mixed Pipe", The Korean Society for Power System Engineering of Spring Conference, pp.7~12 (2007)
- S. D. Kim, "Numerical Analysis of Thermal Flow for Materials of Combined Weapon System in Large Environmental Tester", Spring and Autumn Conference of the Korean Society of Mechanical Engineers, pp.3281~3286 (2007)
- Dassault Systems Solidworks Co., "Solidworks Flow Simulation Manual", ~ (2016)