본문 바로가기
KERD
논문KCI 등재

Habitability evaluation considering various input parameters for main control benchboard fire in the main control room

3

조회

0

다운로드

1

인용

0

참고문헌

키워드

주제분류원자력공학

초록

In this study, operator habitability was numerically evaluated in the event of a fire at the main control bench board (MCB) in a reference main control room (MCR). It was investigated if evacuation variables including hot gas layer temperature (HGLT), heat flux (HF), and optical density (OD) at 1.8 m from the MCR floor exceed the reference evacuation criteria provided in NUREG/CR-6850. For a fire model validation, the simulation results of the reference MCR were compared with existing experimental results on the same reference MCR. In the simulation, various input parameters were applied to the MCB panel fire scenario: MCR height, peak heat release rate (HRR) of a panel, number of panels where fire propagation occurs, fire propagation time, door open/close conditions, and mechanical ventilation operation. A specialized-average HRR (SAHRR) concept was newly devised to comprehensively investigate how the various input parameters affect the operator’s habitability. Peak values of the evacuation variables normalized by evacuation criteria of NUREG/CR-6850 were well-correlated as the power function of the SAHRR for the various input parameters. In addition, the evacuation time map was newly utilized to investigate how the evacuation time for different SAHRR was affected by changing the various input parameters. In the previous studies, it was found that the OD is the most dominant variable to determine the MCR evacuation time. In this study, however, the evacuation time map showed that the HF is the most dominant factor at the condition of without-mechanical ventilation for the MCR with a partiallyopen false ceiling, but the OD is the most dominant factor for all the other conditions. Therefore, the method using the SAHRR and the evacuation time map was very useful to effectively and comprehensively evaluate the operator habitability for the various input parameters in the event of MCB fires for the reference MCR.

Abstract

In this study, operator habitability was numerically evaluated in the event of a fire at the main control bench board (MCB) in a reference main control room (MCR). It was investigated if evacuation variables including hot gas layer temperature (HGLT), heat flux (HF), and optical density (OD) at 1.8 m from the MCR floor exceed the reference evacuation criteria provided in NUREG/CR-6850. For a fire model validation, the simulation results of the reference MCR were compared with existing experimental results on the same reference MCR. In the simulation, various input parameters were applied to the MCB panel fire scenario: MCR height, peak heat release rate (HRR) of a panel, number of panels where fire propagation occurs, fire propagation time, door open/close conditions, and mechanical ventilation operation. A specialized-average HRR (SAHRR) concept was newly devised to comprehensively investigate how the various input parameters affect the operator’s habitability. Peak values of the evacuation variables normalized by evacuation criteria of NUREG/CR-6850 were well-correlated as the power function of the SAHRR for the various input parameters. In addition, the evacuation time map was newly utilized to investigate how the evacuation time for different SAHRR was affected by changing the various input parameters. In the previous studies, it was found that the OD is the most dominant variable to determine the MCR evacuation time. In this study, however, the evacuation time map showed that the HF is the most dominant factor at the condition of without-mechanical ventilation for the MCR with a partiallyopen false ceiling, but the OD is the most dominant factor for all the other conditions. Therefore, the method using the SAHRR and the evacuation time map was very useful to effectively and comprehensively evaluate the operator habitability for the various input parameters in the event of MCB fires for the reference MCR.

참고문헌 (16)

  1. Verification and Validation of Selected Fire Models for Nuclear Power Plant Applications, "U.S. NRC", United States Nuclear Regulatory Commission, ~, pp.NUREG 1824 (2007)
  2. EPRI, "NRC-RES Fire PRA Methodology for Nuclear Power Facilities Detailed Methodology (No. NUREG", CR-6850, EPRI 1011989 Final Report), Nuclear Regulatory Commission, pp.2005, ~
  3. Fire Protection for Nuclear Power Plants, Regulatory Guide 1.189, "U. S. NRC", US Nuclear Regulatory Commission, ~ (2009)
  4. 강대일, "국내 원자력발전소의 주제어실 화재피난 리스크 평가를 위한 화재 시뮬레이션", 한국안전학회지, 29(4), pp.199~207 (2014), 한국안전학회
  5. Y.H. Jung, "A Study on Fire Modeling of Main Control Benchboard Fire Scenarios for Evaluation of Main Control Room Habitability Conditions", Transactions of the Korean Nuclear Society Autumn Meeting, pp.9~10 (2019)
  6. D. I. Kang, "Risk Assessment of Main Control Room Fires for Domestic NPP Based on NUREG-2178"", Transactions of the Korean Nuclear Society Virtual Spring Meeting (2020)
  7. 한호식, "민감도 분석을 이용한 원전 주제어실의 케비닛 화재에 대한 거주성 평가", 한국화재소방학회 논문지, 31(2), pp.52~60 (2017), 한국화재소방학회[DOI]
  8. L. Sun, "Computational fluid dynamics modeling of fire and human evacuation for nuclear applications,", Journal of Nuclear Engineering and Radiation Science, 6(1) (2020)
  9. Nuclear Power Plant Fire Modeling Analysis Guidelines, "U. S. NRC", United States Nuclear Regulatory Commission, ~, pp.NUREG-1934 (2012)
  10. Morgan J. Hurley, "SFPE Handbook of Fire Protection Engineering" (2015), Springer
  11. A.F. Abd El-Aal, "Safest and shortest exit algorithm for NPP fire evacuation", Applied Engineering, 5(1) (2021)
  12. I.H. Kim, "Effect of HVAC operation during the fire in the control room", Proceedings of 2019 Spring Annual Conference, Korean Institute of Fire Science & Engineering, pp.73~74 (2019)
  13. Refining and characterizing heat release rates from electrical enclosures during fire (RACHELLE-FIRE), in: Peak Heat Release Rates and Effect of Obstructed Plume, "U. S. NRC-RES", EPRI, ~, pp.NUREG-2178 Vol. 1 and EPRI 3002005578, vol. 1 (2015)
  14. Fire dynamics tools (FDTs); quantitative fire hazard analysis methods for the U.S. Nuclear regulatory commission fire protection inspection program, "N. Iqbal", NUREG, ~, pp.NUREG-1805 (2004)
  15. Verification and validation of selected fire models for nuclear power plant applicationsefinal report, "NRC, US", ~, pp.No. NUREG-1824 (2016)
  16. R.D. Peacock, "CFASTeConsolidated Model of Fire Growth and Smoke Transport, vol. 1, Technical Reference Guide", ~

관련 논문AI추천

이 간행물의 다른 논문 (39건)