고온 고압용 용접형 판형 열교환기 전열 성능에 관한 연구

A Study on Thermal Performances of Welded Plate Heat Exchanger for High Temperature and Pressure

2

조회

0

다운로드

1

인용

0

참고문헌

키워드

주제분류기계공학

초록

A gasketed plate heat exchanger(GPHE) requires a much smaller installation space than a shell & tube heat exchanger because of its compact and good thermal performances. However, GPHEs have a disadvantage of being relatively vulnerable to high temperature and pressure due to rubber gaskets. To overcome a GPHEs’ disadvantage, Welded Block type Plate Heat Exchangers(WBPHE) have been developed. The flow pattern and heat transfer principle of WBPHE are very similar to GPHEs, so they are very compact and can be applied to high temperature and pressure. In this study, the structure and characteristics of WBPHE are briefly introduced, and its thermal performances were conducted experimentally using hot and cold water in the Reynolds number’s range from 5,500 to 10,000. Test results were compared with the experimental correlations of other researchers, which shows that significant deviations were noticed in the heat transfer coefficient predictions with a deviation range from 31% to 85%. The previous friction factor correlations also predicted the current results with big errors from 25% to 45%. These deviations are expected to be due to different chevron angles between previous studies and the current study, and also the end-plate effect is expected to be one of the potential causes that led to these deviations.

Abstract

A gasketed plate heat exchanger(GPHE) requires a much smaller installation space than a shell & tube heat exchanger because of its compact and good thermal performances. However, GPHEs have a disadvantage of being relatively vulnerable to high temperature and pressure due to rubber gaskets. To overcome a GPHEs’ disadvantage, Welded Block type Plate Heat Exchangers(WBPHE) have been developed. The flow pattern and heat transfer principle of WBPHE are very similar to GPHEs, so they are very compact and can be applied to high temperature and pressure. In this study, the structure and characteristics of WBPHE are briefly introduced, and its thermal performances were conducted experimentally using hot and cold water in the Reynolds number’s range from 5,500 to 10,000. Test results were compared with the experimental correlations of other researchers, which shows that significant deviations were noticed in the heat transfer coefficient predictions with a deviation range from 31% to 85%. The previous friction factor correlations also predicted the current results with big errors from 25% to 45%. These deviations are expected to be due to different chevron angles between previous studies and the current study, and also the end-plate effect is expected to be one of the potential causes that led to these deviations.

참고문헌 (9)

  1. AHRI, "Performance Rating of Liquid to Liquid Heat Exchangers", AHRI, 8~ (2015)
  2. Heat Transfer and Friction Characteristics of Turbulator Radiator Tubes, "P. Farrell", SAE, ~, pp.SAE Technical Paper Series, No. 910197 (1991)
  3. Shah, R. K., "Heat Transfer Equipment Design", pp.227~254 (1988), Hemisphere
  4. R. A. Bounopane, "Heat Transfer Design Method for Plate Heat Exchanger", Chemical Engineering Progress, 59(7), pp.57~61 (1963)
  5. J. Marriott, "Where and How to Use Plate Heat Exchangers", Chemical Engineering, 78(8), pp.127~134 (1971)
  6. Jae-Hong Park, "Evaporation Heat Transfer and Pressure Drop Characteristics of R-134a in the Oblong Shell and Plate Heat Exchanger", Journal of Mechanical Science and Technology, 18(12), pp.2284~2293 (2004), 대한기계학회
  7. L. Wang, "Plate Heat Exchangers", pp.90~ (2007), WIT Press
  8. M. F. Edwards, "Heat Transfer and Pressure Drop Characteristics of a Plate Heat Exchanger Using Newtonian and Non-Newtonian Liquids", The Chemical Engineer, 259(1), pp.286~288 (1974)
  9. A. Cooper, "Recover More Heat With Plate Heat Exchangers", The Chemical Engineer, 259(1), pp.280~285 (1974)