장배관 가변용량 공조시스템의 난방성능에 대한 실험 연구
Experimental study on heating performance of variable capacity A/C system with long pipes
0
조회
0
다운로드
1
인용
0
참고문헌
키워드
초록
In the present study, a calorimeter was used to experimentally investigate the heating capacity and COP changes according to the pipe length of a variable capacity A/C system with long pipes. Cooling capacity, COP, and compressor discharge temperature were obtained by changing pipe lengths and loading duties at fixed indoor and outdoor temperatures. And the operation status and cycle change process of the A/C system were investigated using some experimental data and P-h diagrams. As the pipe length changes, the heat transfer within the cycle and the operating load of the compressor change, so the heating capacity and COP of the system change. At the same loading duty, as the pipe length increases, the heating capacity and COP decrease. As the loading duty increased, the heating capacity increased almost linearly, but the COP decreased. Since the long pipe experimental value for the compressor discharge temperature has a temperature deviation of up to 17℃(50m, L/D : 10/10) from the correlation equation, the optimal correlation equation must be derived through additional research.
Abstract
In the present study, a calorimeter was used to experimentally investigate the heating capacity and COP changes according to the pipe length of a variable capacity A/C system with long pipes. Cooling capacity, COP, and compressor discharge temperature were obtained by changing pipe lengths and loading duties at fixed indoor and outdoor temperatures. And the operation status and cycle change process of the A/C system were investigated using some experimental data and P-h diagrams. As the pipe length changes, the heat transfer within the cycle and the operating load of the compressor change, so the heating capacity and COP of the system change. At the same loading duty, as the pipe length increases, the heating capacity and COP decrease. As the loading duty increased, the heating capacity increased almost linearly, but the COP decreased. Since the long pipe experimental value for the compressor discharge temperature has a temperature deviation of up to 17℃(50m, L/D : 10/10) from the correlation equation, the optimal correlation equation must be derived through additional research.
참고문헌 (8)
- C. K. Rice, "Comparative analysis of single and continuously variable-capacity heat pump Concepts", Proc. of the DOE, 1985, 57~65
- Y. C. Kwon, "Performance of compressor with variable capacity", Journal of Energy Engineering, 13(3), pp.214~218 (2004)
- Y. S. Lee, "An experimental study on the cooling and heating characteristics of system air-conditioner using the digital scroll compressor", Proceeding of the SAREK, pp.575~580 (2002)
- Y. H. Jun, "Experimental study on performance evaluation of system air-conditioner using compressor of PWM and inverter method(cooling and heating characteristics)", Korean Journal of Air-Conditioning and Refrigeration Engineering, 15(9), pp.783~743 (2003)
- B. D. Park, "The variation of multi air conditioner operation characteristics with the arrangements of connection pipe lengths", Solar energy, 20(4), pp.45~752 (2000)
- Y. C. kwon, "Experimental study on cooling performance of variable capacity A", C system, 2024, pp.26(2), 257~262
- Y. C. kwon, "Experimental study on heating performance of variable capacity A", C system, 2024, pp.26(2), 311~316
- "KS C 9306, Air-conditioner", Korean Agency for Technology and Standard, ~ (2017)