장배관 가변용량 공조시스템의 냉방성능에 대한 실험 연구
Experimental study on cooling performance of variable capacity A/C system with long pipes
2
조회
0
다운로드
1
인용
0
참고문헌
키워드
초록
In the present study, a calorimeter was used to experimentally investigate the cooling capacity and COP changes according to the pipe length of a variable capacity A/C system with long pipes. Cooling capacity, COP, and compressor discharge temperature were obtained by changing pipe length and loading duty. And the operation status and cycle change process of the A/C system were investigated using some experimental data and P-h diagrams. In long pipes, the pressure drop increases and the operating load on the compressor increases. Additionally, at the same loading duty, cooling capacity and COP decrease and the compressor discharge temperature increases. As loading duty increases, cooling capacity and compressor power consumption increase. Since the temperature deviation between the experimental value and the correlation equation for the discharge temperature of the long-pipe compressor shows a maximum of 10.5℃(50m, L/D : 20/0), the existing correlation equation needs to be modified.
Abstract
In the present study, a calorimeter was used to experimentally investigate the cooling capacity and COP changes according to the pipe length of a variable capacity A/C system with long pipes. Cooling capacity, COP, and compressor discharge temperature were obtained by changing pipe length and loading duty. And the operation status and cycle change process of the A/C system were investigated using some experimental data and P-h diagrams. In long pipes, the pressure drop increases and the operating load on the compressor increases. Additionally, at the same loading duty, cooling capacity and COP decrease and the compressor discharge temperature increases. As loading duty increases, cooling capacity and compressor power consumption increase. Since the temperature deviation between the experimental value and the correlation equation for the discharge temperature of the long-pipe compressor shows a maximum of 10.5℃(50m, L/D : 20/0), the existing correlation equation needs to be modified.
참고문헌 (9)
- C. K. Rice, "Comparative analysis of single and continuously variable-capacity heat pump Concepts", Proc. of the DOE, 1985, 57~65
- Y. C. Kwon, "Performance of compressor with variable capacity", Journal of Energy Engineering, 13(3), pp.214~218 (2004)
- Y. S. Lee, "An experimental study on the cooling and heating characteristics of system air-conditioner using the digital scroll compressor", Proceeding of the SAREK, pp.575~580 (2002)
- Y. H. Jun, "Experimental study on performance evaluation of system air-conditioner using compressor of PWM and inverter method(cooling and heating characteristics)", Korean Journal of Air-Conditioning and Refrigeration Engineering, 15(9), pp.783~743 (2003)
- B. D Park, "The variation of multi air conditioner operation characteristics with the arrangements of connection pipe lengths", Solar energy, 20(4), pp.45~752 (2000)
- Y. C. kwon, "Experimental study on cooling performance of variable capacity A", C system, 2024, pp.26(2), 257~262
- Y. C. kwon, "Experimental study on heating performance of variable capacity A", C system, 2024, pp.26(2), 311~316
- J. S. Kim, "Experimental study on heating performance of heat pump chiller under overload, frost and defrost conditions", Korea Journal of Air-Conditioning and Refrigeration Engineering, 23(7), pp.477~482 (2011)
- "KS C 9306, Air-conditioner", Korean Agency for Technology and Standard, ~ (2017)