가변형 공조시스템의 냉방특성에 대한 실험 연구
Experimental Study on Cooling Characteristics of Variable A/C System
0
조회
0
다운로드
0
인용
0
참고문헌
키워드
초록
In this study, the calorimeter was used to experimentally investigate the cooling characteristics of the variable A/C system according to changes in loading time and outdoor dry bulb temperature. The cooling capacity, COP and compressor discharge temperature were measured while changing the loading time of the compressor. To develop the correlation for compressor discharge temperature, loading time, indoor and outdoor dry bulb temperatures, evaporation and condensation temperatures were considered as operating variables. As the loading time increased, the cooling capacity and COP increased. The cooling capacity increased linearly with the loading time. The COP increased more at low loading times than at high loading times. The change in condensing temperature according to the loading time had a small temperature fluctuation range, and the evaporation temperature decreased linearly. The compressor discharge temperature increased linearly with the loading time and outdoor temperature, and the maximum deviation between the experimental value and the correlation was within about 2℃.
Abstract
In this study, the calorimeter was used to experimentally investigate the cooling characteristics of the variable A/C system according to changes in loading time and outdoor dry bulb temperature. The cooling capacity, COP and compressor discharge temperature were measured while changing the loading time of the compressor. To develop the correlation for compressor discharge temperature, loading time, indoor and outdoor dry bulb temperatures, evaporation and condensation temperatures were considered as operating variables. As the loading time increased, the cooling capacity and COP increased. The cooling capacity increased linearly with the loading time. The COP increased more at low loading times than at high loading times. The change in condensing temperature according to the loading time had a small temperature fluctuation range, and the evaporation temperature decreased linearly. The compressor discharge temperature increased linearly with the loading time and outdoor temperature, and the maximum deviation between the experimental value and the correlation was within about 2℃.
참고문헌 (6)
- S. M. Baek, "Characteristics of capacity control of variable speed water cooler with the electronic expansion valve open", close degree, 2010, pp.34(2), 282~288
- Y. H. Jun, "Experimental study on performance evaluation of system air-conditioner using compressor of PWM and inverter method(cooling and heating characteristics)", Korean Journal of Air-Conditioning and Refrigeration Engineering, 15(9), pp.783~743 (2003)
- D. H. Yang, "Experimental study on cooling performance characteristics of 2 room simultaneous operation of multi-A", C, 2018, pp.20(5), 612~617
- Y. C. Kwon, "Experimental study on cooling performance of variable capacity A", C system with long pipes, 2024, pp.26(3), 477~482
- B. H. Kim, "An experimental investigation on the variation of heating performance due to the refrigerant flow control in a variable-speed heat pump", Journal of Korean Society of Mechanical Technology, 13(8), pp.746~756 (2001)
- "KS C 9306, “Air-conditioner”", Korean Agency for Technology and Standard, ~ (2017)