천장복사냉방 패널의 냉방용량 설계에서 플레넘 부하의 영향

Effects of Plenum Load on Cooling Capacity Design of Ceiling Radiant Cooling Panels

1

조회

0

다운로드

0

인용

0

참고문헌

키워드

주제분류기타공학

초록

This study investigated the impact of the plenum load on the cooling capacity of ceiling radiant cooling panel (CRCP) systems. A two-dimensional simulation model using Physibel BISCO was developed to represent a small room (3.8 m (L) × 2.9 m (H)) equipped with CRCPs. To analyze the plenum load impact depending on the CRCP type (top insulation, and open- or closed-type installation), three cases were considered: closed-type with top insulation (Case 1), closed-type without top insulation (Case 2), and open-type without top insulation (Case 3). The simulation results showed that the presence of the plenum load increased the plenum air temperature and caused the CRCP to absorb part of the plenum load, consequently leading to the enhanced cooling capacity of the CRCPs. When the plenum load increased to 10%–20% of the room load, the cooling capacity was enhanced by 7.9% ~ 16.8%, compared to the case without a plenum load. This implied that CRCPs could be undersized when they are designed without considering the plenum load. Furthermore, the cooling capacity showed a greater enhancement in the CRCPs without top insulation (Cases 2 and 3) than in those with top insulation (Case 1). Particularly, a higher cooling capacity was obtained with a higher water temperature when applying CRCPs without top insulation. The results suggested that open-type CRCPs without top insulation would be a good cooling solution for a room with a plenum because they are suitable for removing the plenum load even at relatively high water temperatures.

Abstract

This study investigated the impact of the plenum load on the cooling capacity of ceiling radiant cooling panel (CRCP) systems. A two-dimensional simulation model using Physibel BISCO was developed to represent a small room (3.8 m (L) × 2.9 m (H)) equipped with CRCPs. To analyze the plenum load impact depending on the CRCP type (top insulation, and open- or closed-type installation), three cases were considered: closed-type with top insulation (Case 1), closed-type without top insulation (Case 2), and open-type without top insulation (Case 3). The simulation results showed that the presence of the plenum load increased the plenum air temperature and caused the CRCP to absorb part of the plenum load, consequently leading to the enhanced cooling capacity of the CRCPs. When the plenum load increased to 10%–20% of the room load, the cooling capacity was enhanced by 7.9% ~ 16.8%, compared to the case without a plenum load. This implied that CRCPs could be undersized when they are designed without considering the plenum load. Furthermore, the cooling capacity showed a greater enhancement in the CRCPs without top insulation (Cases 2 and 3) than in those with top insulation (Case 1). Particularly, a higher cooling capacity was obtained with a higher water temperature when applying CRCPs without top insulation. The results suggested that open-type CRCPs without top insulation would be a good cooling solution for a room with a plenum because they are suitable for removing the plenum load even at relatively high water temperatures.

참고문헌 (16)

  1. Babiak, J., "Low Temperature Heating and High Temperature Cooling: REHVA GUIDEBOOK No 7", REHVA, ~ (2007)
  2. Rhee, K. N., "A 50 Year Review of Basic and Applied Research in Radiant Heating and Cooling Systems for the Built Environment", Building and Environment, 91, pp.166~190 (2015)
  3. Lee, J., "Case Study of HD Global R&D Center : Energy Efficiency Improvement Measures for a Large-Scale Office", Research Facility(in Korean), 2023, pp.24(3), 21~31
  4. Chung, J., "Case Study of Mechanical Systems of New LH Headquarters(in Korean)", Korean Institute of Architectural Sustainable Environment and Building Systems, 10(1), pp.30~35 (2016)
  5. Lim, J., "ISO 18566, the International Standard on the Design, Test Methods and Control of Hydronic Radiant Heating and Cooling Panel Systems", REHVA Journal, 5, pp.64~72 (2016)
  6. ANSI, "Standard 138-Method of Testing for Rating Ceiling Panels for Sensible Heating and Cooling", ANSI, 2013
  7. CEN, "EN 14240: Ventilation for Buildings–Chilled Ceilings–Testing and Rating", CEN, ~ (2004)
  8. ASHARE, "ASHRAE Handbook – Fundamental. 18.42", ASHRAE, ~ (2021)
  9. Shin, M. S., "Enhancement of Cooling Capacity through Open-Type Installation of Cooling Radiant Ceiling Panel Systems", Building and Environment, 148, pp.417~432 (2019)
  10. Choi, J. S., "Cooling Performance Evaluation of a Fan-Assisted Ceiling Radiant Cooling Panel System", Energy and Buildings, 281, pp.112760~ (2023)
  11. Shinoda, J., "Improved Cooling Performance Testing of Radiant Ceiling Panels", The REHVA European HVAC Journal, 59(3), pp.30~34 (2022)
  12. Shinoda, J., "Improvements to the Cooling Capacity Measurements of Suspended Radiant Ceiling Panels to Prevent Under-Sizing", Journal of Building Engineering, 51, pp.104242~ (2022)
  13. Cho, J., "A Bi-directional Systematic Design Approach to Energy Optimization for Energy-Efficient Buildings", Energy and Buildings, 120, pp.135~144 (2016)
  14. Schiavon, S., "Influence of Raised Floor on Zone Design Cooling Load in Commercial Buildings", Energy and Buildings, 42(8), pp.1182~1191 (2010)
  15. Park, S., "A Study on the Evaluation of the Cooling Capacity of Radiant Ceiling Panel According to the Panel Type", Journal of Architectural Institute of Korea, 30(12), pp.299~306 (2014)
  16. "Giacomini S.p.A" (2023)[URL]