변풍량 시스템에서 공조기 급기팬의 발열 인자 분석
Analysis of Influencing Factor on Supply Fan Temperature Rise of Air Handling Unit in Variable Air Volume System
0
조회
0
다운로드
0
인용
0
참고문헌
키워드
초록
An economizer system reduces the energy consumed by an air-handling unit while maintaining indoor comfort. The economizer system reduces the cooling load and energy consumption by adjusting the amount of outside air introduced when the outside temperature is lower than the indoor temperature. The fan operation in the air-handling unit causes pressure losses, such as heat, vibration, and noise. The heat generated from the air supply fan causes a temperature difference between the front and rear ends of the fan, and the actual supplied air temperature differs from the set temperature of the system. In this study, the factors affecting the temperature rise of the air supply fan were analyzed experimentally, and the terminal damper opening rate and fan speed were selected as variables to check the heat generation of the air supply fan owing to the changes in the air flow rate and differential pressure in the variable air flow system. The experiment confirmed the temperature difference according to the changes in the air flow rate and differential pressure. Additionally, using multiple regression analysis, a model was developed for predicting the increase in the air supply fan temperature. The terminal damper opening rate and fan speed were set as the independent variables, and the temperature difference was set as the dependent variable. A comparison of the predicted and experimental values using the developed prediction model revealed that R² was 0.95.
Abstract
An economizer system reduces the energy consumed by an air-handling unit while maintaining indoor comfort. The economizer system reduces the cooling load and energy consumption by adjusting the amount of outside air introduced when the outside temperature is lower than the indoor temperature. The fan operation in the air-handling unit causes pressure losses, such as heat, vibration, and noise. The heat generated from the air supply fan causes a temperature difference between the front and rear ends of the fan, and the actual supplied air temperature differs from the set temperature of the system. In this study, the factors affecting the temperature rise of the air supply fan were analyzed experimentally, and the terminal damper opening rate and fan speed were selected as variables to check the heat generation of the air supply fan owing to the changes in the air flow rate and differential pressure in the variable air flow system. The experiment confirmed the temperature difference according to the changes in the air flow rate and differential pressure. Additionally, using multiple regression analysis, a model was developed for predicting the increase in the air supply fan temperature. The terminal damper opening rate and fan speed were set as the independent variables, and the temperature difference was set as the dependent variable. A comparison of the predicted and experimental values using the developed prediction model revealed that R² was 0.95.
참고문헌 (19)
- IEA, "Tracking Clean Energy Progress", ~ (2022)
- Kim, C. H., "Analysis of Energy Saving Potential in High-Performance Building Technologies under Korean Climatic Conditions", Energies, 11(4), pp.884~ (2018)
- Kim, C. H., "Comprehensive Analysis of Energy Consumption Rate and New Technology Trend in High-Performance Buildings related with Different Climatic Zones", Journal of the Architectural Institute of Korea Structure & Construction, 34(11), pp.63~72 (2018)
- Park, M. K., "Air-handling-unit Discharge Air Temperature Reset Based on Outdoor Air Temperature and Cooling Energy Performance in an Office Building", Journal of Energy Engineering, 146(3), pp.04020013~ (2020)
- Son, J. E., "Comparison of Cooling-Energy Performance Depending on the Economizer-Control Methods in an Office Building", Korean Journal of Air-Conditioning and Refrigeration Engineering, 27(8), pp.432~439 (2015)
- Seong, N. C., "Evaluation of Operation Performance Depending on the Control Methods and Set Point Variation of the Economizer System", Journal of Korean Institute of Architectural Sustainable Environment and Building Systems, 16(1), pp.94~107 (2022)
- Wichman, A., "A Smart Mixed-Air Temperature Sensor", HVAC&R Research, 15(1), pp.101~115 (2009)
- Bae, H. J., "A Study on the Reduction of Entry Loss by Inner Structure in Square Hood in Industrial Ventilation System", Korean Society for Environmental Sanitary Engineers, 18(3), pp.27~34 (2003)
- Lee, J. W., "Survey Study of Optimal Cooling Equipment Capacity of the Large Hospitals in Busan City", Journal of the Korea Institute of Ecological Architecture and Environment, 14(6), pp.105~110 (2014)
- Robert McDowall, "Fundamentals of Air System Design", ASHRAE, ~ (2010)
- Joanna Mauer, "Fan Energy lndex : A New Metric for Fan Efficiency", Appliance DESIGN, ~ (2018)
- Development of a Virtual Metering Method for Characterizing Energy Flows in Air Handling Units, "Drwazeh, D.", IEEE, ~ (2019)
- "HVAC and Plumbing Encyclopedia", Korean Journal of Air-Conditioning and Refrigeration Engineering (2010)
- Topfer, K., "Electrical Energy Equipment : Fans and Blower UNEP", ~ (2006)
- Lee, J. H., "Analysis of Energy Saving Effect in Variation of Supply Air Temperature of Economizer System", Journal of Korean Institute of Architectural Sustainable Environment and Building Systems, 11(5), pp.415~424 (2017)
- Lee, M. K., "Developing The Prediction Program of Heat and Cooling Loads by Modified Bin Methods", Journal of the Korean Solar Energy Society, 21(4), pp.21~28 (2001)
- ASHRAE, "ASHRAE Standard 90.1", ~ (2013)
- ASHRAE, "ASHRAE Standard 62.1", ~ (2010)
- Cha, K. H., "Development of the Deterioration Models for the Port Structures by the Multiple Regression Analysis and Markov Chain", Journal of the Computational Structural Engineering Institute of Korea, 28(3), pp.229~240 (2015)