초록

The feasibility of using hydrazine for inhibiting pitting corrosion in copper sprinkler tubes was investigatedby examining microscopical and structural evolution of corrosion by-products with SEM, EDS, andXRD. Hydrazine removed dissolved oxygen and reduced CuO and Cu2O as well. The stable phasewas changed from CuO to Cu2O or Cu depending on hydrazine concentration. Hydrazine concentrationof 500 ppm could convert all CuO corrosion by-products to Cu2O. In a tightly sealed acryl tube filledwith aqueous solution of 500 ppm hydrazine, octahedral Cu2O particles were formed while plate-likestructures with high concentration of Cu, O, N and C were formed near a corrosion pit. The insidestructure of a corrosion pit was not altered by hydrazine aqueous solution. Uniform corrosion of copperwas almost completely stopped in aqueous solution of 500 ppm hydrazine. Corrosion potential of acopper plate was linearly dependent on log (hydrazine concentration). The concept of stopping pittingcorrosion reaction by suppressing oxygen reduction reaction could be verified by applying this methodto a reasonable number of real sprinkler systems before full-scale application.

Abstract

The feasibility of using hydrazine for inhibiting pitting corrosion in copper sprinkler tubes was investigatedby examining microscopical and structural evolution of corrosion by-products with SEM, EDS, andXRD. Hydrazine removed dissolved oxygen and reduced CuO and Cu2O as well. The stable phasewas changed from CuO to Cu2O or Cu depending on hydrazine concentration. Hydrazine concentrationof 500 ppm could convert all CuO corrosion by-products to Cu2O. In a tightly sealed acryl tube filledwith aqueous solution of 500 ppm hydrazine, octahedral Cu2O particles were formed while plate-likestructures with high concentration of Cu, O, N and C were formed near a corrosion pit. The insidestructure of a corrosion pit was not altered by hydrazine aqueous solution. Uniform corrosion of copperwas almost completely stopped in aqueous solution of 500 ppm hydrazine. Corrosion potential of acopper plate was linearly dependent on log (hydrazine concentration). The concept of stopping pittingcorrosion reaction by suppressing oxygen reduction reaction could be verified by applying this methodto a reasonable number of real sprinkler systems before full-scale application.

참고문헌 (11)

  1. 이재봉, "스프링클러 동배관의 공식부식 발생원인", CORROSION SCIENCE AND TECHNOLOGY, 13(1), pp.6~14 (2014), 한국부식방식학회[DOI]
  2. S. H. Suh, , Eng. Fail. Anal., 64, pp.111~ (2016)
  3. Research report: Study on the cause of copper tube corrosion, "J-G. Kim", The Korean Institute of Surface Engineering, ~ (2016)
  4. I. B. Butler, , Talanta, 41, pp.211~ (1994)
  5. "Association of Water Technologies - Technical Manual, Boiler Systems 7.0 Chemical Treatment"[URL]
  6. M. Pourbaix, "Atlas of Electrochemical Equilibria in Aqueous Solutions", pp.1~644 (1974), Pergamon Press, NACE
  7. S. Yagi, , J. Electrochem. Soc., 156, pp.D321~ (2009)
  8. S. H. Suh, "Wet type sprinkler system for preventing copper pitting corrosion and method for removing dissolved oxygen in water using the same", Korea Patent pending No. 10-2016-0116277, ~ (2016)
  9. M. Sosa, , Corrosion, 55, pp.1069~ (1999)
  10. D. A. Lytle, , Corros. Sci., 52, pp.1927~ (2010)
  11. E. Sarver, , Int. J. Corros. (2012)

관련 논문AI추천

이 간행물의 다른 논문 (5건)