아황산나트륨을 이용한 스프링클러 동배관 공식 부식 방지
Inhibition of Pitting Corrosion of Copper Tubes in Wet Sprinkler Systems by Sodium Sulfite
2
조회
0
다운로드
3
인용
0
참고문헌
키워드
초록
Inhibition of pitting corrosion of the copper sprinkler tubes by removing dissolved oxygen in water withsodium sulfite was studied on the wet sprinkler systems operated in 258 household sites. First, air in thesprinkler tubing was removed by vacuum pumping. The tube was then filled with sodium sulfite dissolvedin water. Sodium sulfite was very effective in maintaining a very low dissolved oxygen concentration inwater in the sprinkler tube for the observation period of six months. Water leakage from the copper sprinklertube was reduced significantly by using sodium sulfite. Both pitting corrosion process and pitting corrosioninhibition mechanism were investigated by examining microscopical and structural aspects of corrosion pitsformed in failed copper sprinkler tube. Pitting corrosion was caused by pressurized air as well as sedimentssuch as sand particles in copper tubes through oxygen concentration cells. It was confirmed microscopicallythat growth of corrosion pits was stopped by reducing dissolved oxygen concentration to a very level byusing sodium sulfite.
Abstract
Inhibition of pitting corrosion of the copper sprinkler tubes by removing dissolved oxygen in water withsodium sulfite was studied on the wet sprinkler systems operated in 258 household sites. First, air in thesprinkler tubing was removed by vacuum pumping. The tube was then filled with sodium sulfite dissolvedin water. Sodium sulfite was very effective in maintaining a very low dissolved oxygen concentration inwater in the sprinkler tube for the observation period of six months. Water leakage from the copper sprinklertube was reduced significantly by using sodium sulfite. Both pitting corrosion process and pitting corrosioninhibition mechanism were investigated by examining microscopical and structural aspects of corrosion pitsformed in failed copper sprinkler tube. Pitting corrosion was caused by pressurized air as well as sedimentssuch as sand particles in copper tubes through oxygen concentration cells. It was confirmed microscopicallythat growth of corrosion pits was stopped by reducing dissolved oxygen concentration to a very level byusing sodium sulfite.
참고문헌 (14)
- D. A. Lytle, , J. Am. Water Works Ass, 100, pp.115~ (2008)
- H. Cong, , J. Electrochem. Soc., 156, pp.C16~C27 (2009)
- E. Sarver, , J. Am. Water Works Ass, 103, pp.86~ (2011)
- E. Sarver, , Int. J. Corros. (2012)
- M. Edwards, , J. Am. Water Works Ass, 86, pp.74~ (1994)
- "This Old House, How to stop copper pipe corrosion"[URL]
- "BS EN 1057:1996, Copper and copper alloys- Seamless, round copper tubes for water and gas in sanitary and heating applications", ~ (1996)
- 이재봉, "스프링클러 동배관의 공식부식 발생원인", CORROSION SCIENCE AND TECHNOLOGY, 13(1), pp.6~14 (2014), 한국부식방식학회[DOI]
- S. H. Suh, , Eng. Fail. Anal, 64, pp.111~ (2016)
- Research report: Study on the cause of copper tube corrosion, "J-G. Kim", the Korean Institute of Surface Engineering, ~ (2016)
- S. H. Suh, "Wet type sprinkler system for preventing corrosion of metallic water supply tubes", Korea Patent No. 10-1630742 (2016) and 10-1734897, ~ (2017)
- S. H. Suh, "Apparatus and methods for drain, vent and water filling for wet type sprinkler systems", Korea Patent pending No. 10-2017-0032686 and 10-2017-0093215, ~ (2017)
- 서상희, "Use of Hydrazine for Pitting Corrosion Inhibition of Copper Sprinkler Tubes:Reaction of Hydrazine with Corrosion By-Products", CORROSION SCIENCE AND TECHNOLOGY, 16(5), pp.247~256 (2017), 한국부식방식학회[DOI]
- M. Pourbaix, "Atlas of Electrochemical Equilibria in Dissolved waters" (1974), Pergamon Press