본문 바로가기
KERD
논문KCI 등재

ESS 컨테이너 냉각용 루프 열사이폰 열교환기의 다양한 작동유체에 대한 특성과 성능 실험

An Experimental Study on the Characteristics and Performance of Various Working Fluids of a Loop Thermosyphon Heat Exchanger for ESS Container Cooling

1

조회

0

다운로드

2

인용

0

참고문헌

키워드

주제분류기계공학

초록

Experiments were conducted on the operating characteristics and performance of various types of working fluid, filling amount and heat flow rate of a loop thermosyphon for cooling ESS battery container. As results of performance test on various working fluids, HFE-7100 and R-134a as a working fluids showed unstable operating and low performance due to vapor pressure drop, and performance was improved by increasing the number of vapor lines for reducing a pressure drop. In this study, n-pentane was more stable and showed better thermal performance among various working fluids.

Abstract

Experiments were conducted on the operating characteristics and performance of various types of working fluid, filling amount and heat flow rate of a loop thermosyphon for cooling ESS battery container. As results of performance test on various working fluids, HFE-7100 and R-134a as a working fluids showed unstable operating and low performance due to vapor pressure drop, and performance was improved by increasing the number of vapor lines for reducing a pressure drop. In this study, n-pentane was more stable and showed better thermal performance among various working fluids.

참고문헌 (8)

  1. Zhang, Y., "Free cooling technologies for data centers : energy saving mechanism and applications", Energy Procedia, 143, pp.410~415 (2017)
  2. Khodabandeh, R., "Thermal performance of a closed advanced two-phase thermosyphon loop for cooling of radio base stations at different operating conditions", Applied Thermal Engineering, 24(17-18), pp.2643~2655 (2004)
  3. Kim, C. J., "A study on the pulse boiling occurring inside the liquid pool of a closed two-phase thermosyphon", KSME(B), 21(10), pp.1254~1261 (1995)
  4. 도선엽, "비혼합 2유체 열사이폰의 저온시동 특성에 관한 연구", 한국기계기술학회지, 17(2), pp.223~229 (2015), 한국기계기술학회[DOI]
  5. Agunlejika, E. O., "Flow instabilities in a horizontal thermosyphon reboiler loop", Experimental Thermal and Fluid Science, 78, pp.90~99 (2016)
  6. 이기우, "루프형 2상 유동 열사이폰 열교환기에 관한 연구", 설비공학 논문집, 14(9), pp.4~724 (2002), 대한설비공학회
  7. Hwang, K. S., "A closed counter-current two-phase thermosyphon loop of a cold neutron source in HANARO research reactor", KSME(B), 24(8), pp.1038~1045 (2000)
  8. 강환국, "루프 써모사이폰의 작동특성과 열전달 한계 연구", 한국기계기술학회지, 14(3), pp.59~66 (2012), 한국기계기술학회[DOI]