루프 써모사이폰의 작동특성과 열전달 한계 연구
A Study on the Operational Characteristics and Limitation of the Loop Thermosyphon
2
조회
0
다운로드
3
인용
0
참고문헌
키워드
초록
The loop thermosyphon has been designed and tested for cooling several hundreds watt of heat. This cooling system is consisted of copper block, condenser which is fabricated with tubes and fins and transport lines. In this research, operational characteristics and limitation of the loop thermosyphon were investigated as a function of fill charge ratio, thermal load, vapor temperature and effective head. The experimental results shows that the heat transfer limitation is dominated by vapor temperature and effective head. Also, the correlation for the heat transfer limitation is presented and showed good agreement. The evaporating heat transfer coefficient is affected by vapor temperature and heat flux, but the fill charge ratio and liquid head are minor factor.
Abstract
The loop thermosyphon has been designed and tested for cooling several hundreds watt of heat. This cooling system is consisted of copper block, condenser which is fabricated with tubes and fins and transport lines. In this research, operational characteristics and limitation of the loop thermosyphon were investigated as a function of fill charge ratio, thermal load, vapor temperature and effective head. The experimental results shows that the heat transfer limitation is dominated by vapor temperature and effective head. Also, the correlation for the heat transfer limitation is presented and showed good agreement. The evaporating heat transfer coefficient is affected by vapor temperature and heat flux, but the fill charge ratio and liquid head are minor factor.
참고문헌 (11)
- Khodabandeh, R, "Thermal performance of a closed advanced two-phase thermosyphonloop for cooling of radio base stations at different operating conditions", Applied Thermal Engineering, 24(17), pp.2643~2655 (2004)
- Dube, V., "The effects of non-condensable gases on the performance of loopthermosyphon heat exchangers", Applied Thermal Engineering, 24(16), pp.2439~2451 (2004)
- Khodabandeh, R., "Heat transfer, flow regime and instability of a nano- and micro-porous structure evaporator in a two-phase thermosyphonloop", International Journal of Thermal Sciences, 49(7), pp.1183~1192 (2010)
- 이석호, "다양한 규모의 루프형 2상 유동 열사이폰의 시뮬레이션", 설비공학 논문집, 14(5), pp.6~407 (2002), 대한설비공학회
- 장기창, "분리형 써모사이폰의 열전달특성에 관한 실험적 연구", 공기조화 · 냉동공학논문집, 10(9), pp.22~32 (1998)
- Charles C.J., Vincent, "Investigation of the Overall Transient Performance of the Industrial Two-Phase Closed Loop Thermosyphon", Int, J of Heat Mass Transfer, 35(6), pp.1419~1426 (1992)
- 강환국, "VCHP의 작동특성에 관한 연구", 한국기계기술학회지, 11(4), pp.37~43 (2009), 한국기계기술학회
- 강환국, "VCHP를 적용한 냉시동 가능 전력 반도체 냉각기의 작동특성에 관한 연구", 한국기계기술학회지, 12(4), pp.211~217 (2010), 한국기계기술학회
- Mou, K., "Investigation of the Dry-out Limit in Evaporator of the Separate type Heat Pipe", 7th IHPC, pp.475~482 (1991)
- Li J., "Heat Teransport Limits of the Separate Type Heat Pipe", Proc. of the 10th IHPC (1997)
- 윤준용, "유체역학", pp.623~633 (1996), 청문각