Test of the operating characteristics and energy saving performance of a container cooling system that reduces the operating energy of a refrigeration system using a loop thermosyphon heat exchanger that removes heat by temperature difference between outdoor and indoor was performed. As a result of the experiments, when the loop thermosyphon and the refrigeration system were operated simultaneously, the refrigeration system operated intermittently by reducing the heat load. As the temperature difference between indoor and outdoor increased, the operating time of the refrigeration system decreased and the energy efficiency rate increased. Energy efficiency rate showed a tendency to increase with increasing temperature difference, and the predicted correlation of energy efficiency rate using the performance of the loop thermosyphon heat exchanger and the refrigeration system was relatively consistent with the experimental value.
Abstract
Test of the operating characteristics and energy saving performance of a container cooling system that reduces the operating energy of a refrigeration system using a loop thermosyphon heat exchanger that removes heat by temperature difference between outdoor and indoor was performed. As a result of the experiments, when the loop thermosyphon and the refrigeration system were operated simultaneously, the refrigeration system operated intermittently by reducing the heat load. As the temperature difference between indoor and outdoor increased, the operating time of the refrigeration system decreased and the energy efficiency rate increased. Energy efficiency rate showed a tendency to increase with increasing temperature difference, and the predicted correlation of energy efficiency rate using the performance of the loop thermosyphon heat exchanger and the refrigeration system was relatively consistent with the experimental value.
참고문헌 (7)
- Kizilel, R., "An Alternative Cooling System to Enhance the Safety of Li-ion Battery Packs", J. Power Sources, 194, pp.1105~ (2009)
- Gu, W. B., "Thermal-electrochemical Modeling of Battery Systems", J. Electrochem. Soc, 147, pp.2910~ (2000)
- Zhang, Y., "Free Cooling Technologies for Data Centers: Energy Saving Mechanism and Applications", Energy Procedia, 143, pp.410~415 (2017)
- 강환국, "ESS 컨테이너 냉각용 루프 열사이폰 열교환기의 다양한 작동유체에 대한 특성과 성능 실험", 한국기계기술학회지, 22(1), pp.37~43 (2020), 한국기계기술학회[DOI]
- 강환국, "ESS 배터리 컨테이너 냉각용 루프 열사이폰 열교환기의 배열 및 성능인자의 영향에 관한 연구", 한국기계기술학회지, 22(5), pp.891~897 (2020), 한국기계기술학회[DOI]
- 김영득, "이동통신 옥내기지국용 에너지 절약형 하이브리드 냉방기 개발", 한국기계기술학회지, 11(2), pp.59~65 (2009), 한국기계기술학회[DOI]
- 강환국, "루프 써모사이폰의 작동특성과 열전달 한계 연구", 한국기계기술학회지, 14(3), pp.59~66 (2012), 한국기계기술학회[DOI]