The thermal conductivity for the ground heat exchanger installed in the local facilities of greenhouse area at JangSu-Gun in Jeollabuk-Do was analyzed experimentally. For measuring the thermal conductivity of the ground heat exchanger, a bore hole was punched at the size of diameter 150mm, depth 160m. And a closed-type heat exchanger of high density polyethylene at the size of diameter 40mm was installed vertically. The heated water by an electric heater was circulated through the ground heat exchanger with a pump. The inlet/outlet temperatures and the flow rates of this water are measured and the thermal conductivity was calculated. The experimental results were as follows. The inlet/outlet temperatures of the ground heat exchanger were increased rapidly until 7 hours, then they were increased gently and the difference of inlet/outlet temperature was maintained at about 4.5℃. The thermal conductivity calculated by the line source theory was 2.207W/mK.
Abstract
The thermal conductivity for the ground heat exchanger installed in the local facilities of greenhouse area at JangSu-Gun in Jeollabuk-Do was analyzed experimentally. For measuring the thermal conductivity of the ground heat exchanger, a bore hole was punched at the size of diameter 150mm, depth 160m. And a closed-type heat exchanger of high density polyethylene at the size of diameter 40mm was installed vertically. The heated water by an electric heater was circulated through the ground heat exchanger with a pump. The inlet/outlet temperatures and the flow rates of this water are measured and the thermal conductivity was calculated. The experimental results were as follows. The inlet/outlet temperatures of the ground heat exchanger were increased rapidly until 7 hours, then they were increased gently and the difference of inlet/outlet temperature was maintained at about 4.5℃. The thermal conductivity calculated by the line source theory was 2.207W/mK.
참고문헌 (7)
- 변재기, "리조트 건물의 연료전지 구동 지열원 복합열원 하이브리드 히트펌프 냉․난방 시스템 성능에 관한 해석적 연구", 한국기계기술학회지, 12(4), pp.25~31 (2010), 한국기계기술학회
- 정영만, "지중열전도도 측정과 지중열교환기의 열확산 특성 분석", 설비공학 논문집, 20(11), pp.739~745 (2008), 대한설비공학회
- Y. J. Kim, "Performance analysis of ground thermal conductivity by ground heat exchanger", Proceedings of the SAREK 2005 Winter Annual Conference, pp.161~166 (2005)
- K. H. Jung, "Regional distribution of ground thermal conductivity for vertical closed type ground heat exchanger design", Proceedings of the SAREK 2007 Winter Annual Conference, pp.423~428 (2007)
- S. Gehlin, "Thermal response test method development and evaluation", 박사, pp.2002
- P. Mogensen, "Fluid duct wall heat transfer in duct system heat storage", Proceedings of International Conference on Subsurface Heat Storage in Theory and Practice, Stockholm, Sweden, pp.652~657 (1983)