The temperatures with the ground depth, the positions of circulation water in ground heat exchanger were measured and thermal diffusion characteristics with the distances of the direction normal to the borehole was analysed. The deeper the depth of ground, the less the influences of outdoor temperature, but below 10m of ground, there was no influences of ground temperature. When the depth of trench pipe was below the depth of 2m, there was no influence. In the ground of 10m when the distances between the pipe and the other places were above 0.5m, the variations of temperature were less than $1.6^{\circ}C$ and above 2.5m they were less than $0.1^{\circ}C$. When the distances of bore hole were above 5m, there were no. influences of the nearest ground heat exchanger.

Abstract

The temperatures with the ground depth, the positions of circulation water in ground heat exchanger were measured and thermal diffusion characteristics with the distances of the direction normal to the borehole was analysed. The deeper the depth of ground, the less the influences of outdoor temperature, but below 10m of ground, there was no influences of ground temperature. When the depth of trench pipe was below the depth of 2m, there was no influence. In the ground of 10m when the distances between the pipe and the other places were above 0.5m, the variations of temperature were less than $1.6^{\circ}C$ and above 2.5m they were less than $0.1^{\circ}C$. When the distances of bore hole were above 5m, there were no. influences of the nearest ground heat exchanger.

참고문헌 (9)

  1. 우상우, "CFD 해석에 의한 수직형 지열교환기의 성능예측", 한국태양에너지학회 논문집, 27(3), pp.117~126 (2007), 한국태양에너지학회
  2. Koo, K. M., "Heating Performance of a Ground Source Heat Pump System through Actual Operation", Proceedings of the SAREK, Summer Annual Conference, pp.788~793 (2008)
  3. Choi, J. H., "Effect of Some Parameters on Ground Effective Thermal Conductivity", Proceedings of the SAREK, Winter Annual Conference, pp.33~38 (2008)
  4. 정영만, "지중열전도도 측정과 지중열교환기의 열확산 특성 분석", 설비공학 논문집, 20(11), pp.739~745 (2008), 대한설비공학회
  5. Choi, J. M., "Verification experiment of a ground source multi-heat pump at heating season", Proceedings of the SAREK Summer Annual Conference, pp.52~57 (2009)
  6. 최종민, "지열원 물대공기 멀티 히트펌프의 일일 난방 운전 특성에 관한 실증 연구", 설비공학 논문집, 21(9), pp.527~535 (2009), 대한설비공학회
  7. 최종민, "지열원 물대공기 멀티 히트펌프의 냉방 운전 특성에 관한 실증 연구", 설비공학 논문집, 21(5), pp.297~304 (2009), 대한설비공학회
  8. 임효재, "지중열교환기 설치 조건이 지중 유효 열전도도와 보어홀 열저항에 미치는 영향", 설비공학 논문집, 23(2), pp.95~102 (2011), 대한설비공학회
  9. Han, J S., "Geothermal Pump Heating and Cooling System", pp.4~13 (2005), Han Lim Won Pub