본문 바로가기
KERD
논문KCI 등재

10kW 냉동유닛의 냉동사이클 성능에 대한 실험연구

Experimental Study on Refrigeration Cycle Performance of 10kW Refrigerator Unit

0

조회

0

다운로드

0

인용

0

참고문헌

키워드

주제분류기계공학

초록

This experimental study was conducted to investigate the refrigeration cycle performance of a 10kW refrigerator unit using R404A refrigerant. The capacity, COP, and refrigeration cycle of the refrigerator unit were confirmed by changes in refrigerant charging amount and degree of superheat. The cooling capacity and COP of the refrigerator unit showed different tendency according to changes in refrigerant charging amount and degree of superheat. It was confirmed that the performance changes of the refrigerator unit were more dependent on the change in degree of superheat than the refrigerant charging amount. From the capacity, COP, pressure, and p-h diagram, the refrigeration cycle of the refrigerator unit showed the greatest capacity and COP at 4℃ for degree of superheat and 7,400g for the refrigerant charging amount.

Abstract

This experimental study was conducted to investigate the refrigeration cycle performance of a 10kW refrigerator unit using R404A refrigerant. The capacity, COP, and refrigeration cycle of the refrigerator unit were confirmed by changes in refrigerant charging amount and degree of superheat. The cooling capacity and COP of the refrigerator unit showed different tendency according to changes in refrigerant charging amount and degree of superheat. It was confirmed that the performance changes of the refrigerator unit were more dependent on the change in degree of superheat than the refrigerant charging amount. From the capacity, COP, pressure, and p-h diagram, the refrigeration cycle of the refrigerator unit showed the greatest capacity and COP at 4℃ for degree of superheat and 7,400g for the refrigerant charging amount.

참고문헌 (11)

  1. Kang, "Experimental Study on the Cold Insulation Performance of Refrigerator Truck us Latent Heat Storage Materials", SAREK, pp.789~792 (2015)
  2. 신윤찬, "운전조건에 따른 R404A와 R134a를 적용한 냉동탑차용 냉장시스템의 엑서지 비교", 설비공학 논문집, 26(11), pp.497~503 (2014), 대한설비공학회[DOI]
  3. 김상훈, "착상조건에서 R744 냉매 적용 탑차용 냉장시스템의 성능해석", 설비공학 논문집, 25(9), pp.499~505 (2013), 대한설비공학회[DOI]
  4. 명치욱, "R404A와 R744의 냉매를 이용한 냉동탑차 냉장성능 비교에 관한 해석적 연구", 한국자동차공학회 논문집, 19(6), pp.119~125 (2011), 한국자동차공학회
  5. 오후규, "R744-R404A 캐스케이드 냉동시스템의 최적 냉매 충전을 위한 질량유량비 분석", 한국마린엔지니어링학회지, 37(6), pp.575~581 (2013), 한국마린엔지니어링학회[DOI]
  6. 원성필, "공기사이클 냉동시스템의 성능해석", 설비공학 논문집, 24(9), pp.671~678 (2012), 대한설비공학회[DOI]
  7. Yang, H. M., "Prediction of Performance Variation of Compressor by Changing Refrigerants", KSFM, pp.146~147 (2016)
  8. "Korea Refrigeration & Air-conditioning Assessment Center", Psychrometric calorimeter, ~ (2013)
  9. "ASHRAE Standard 41.2, Standard Method for Laboratory Air-Flow Measurement", ASHRAE, ~ (1987)
  10. "Agreement on the International Carriage of Perishable Foodstuffs and on the Special Equipment to be Used for such Carriage(ATP)", ~ (2014)
  11. Cho, H. H., "Experimental Study on the Variation of the Optimal charge with Cycle option in the CO2 Refrigeration", SAREK, pp.398~403 (2005)

관련 논문AI추천

이 간행물의 다른 논문 (29건)