본문 바로가기
KERD
논문KCI 등재

실내·외 공기질 연계 IoT 자동제어 환기장치의 에너지 사용량 분석

Energy Consumption Analysis of IoT Automatic Ventilation Systems with Integrated Indoor and Outdoor Air Quality Control

3

조회

0

다운로드

0

인용

0

참고문헌

키워드

주제분류기계공학

초록

The importance of indoor air quality has significantly increased after the COVID-19 pandemic. This study analyzed the energy consumption of a ventilation system based on various operating methods considering indoor and outdoor conditions. From March to May 2024, experiments were conducted on ventilation systems installed in a hospital in Incheon, comparing the experimental and control groups. The results showed that using the bypass mode in the experimental group reduced total energy consumption by 25.34% compared to the control group. Additionally, utilizing the air-cleaner mode further reduced energy use. This study demonstrates that optimal use of bypass and air-cleaner modes can enhance energy efficiency. Further research is needed to verify long-term applicability under diverse conditions.

Abstract

The importance of indoor air quality has significantly increased after the COVID-19 pandemic. This study analyzed the energy consumption of a ventilation system based on various operating methods considering indoor and outdoor conditions. From March to May 2024, experiments were conducted on ventilation systems installed in a hospital in Incheon, comparing the experimental and control groups. The results showed that using the bypass mode in the experimental group reduced total energy consumption by 25.34% compared to the control group. Additionally, utilizing the air-cleaner mode further reduced energy use. This study demonstrates that optimal use of bypass and air-cleaner modes can enhance energy efficiency. Further research is needed to verify long-term applicability under diverse conditions.

참고문헌 (8)

  1. A Propose of the Ventilation System Consideringthe Energy Performance and Cost-effectiveness, "LH Land and Housing Institute", ~ (2015)
  2. Suwon Song, "Analysis of Indoor Air Quality (IAQ)according to the Operation Conditions of an Air-cleaner and Natural Ventilation through Windows in A Small Office", Proceedings of the Summer Conference of the Society of Air-Conditioning and Refrigerating Engineers of Korea, pp.442~445 (2019)
  3. Seokgeun Kim, "(A) study on an energy-efficient outdoor air supply control method in apartment ventilation system", Doctor, pp.2009
  4. Taegeon Lim, "A Study on The Performance of a Heat Recovery Ventilator According to the Properties of Spacers", Korean journal of air-conditioning and refrigeration engineering, 24(3), pp.224~229 (2012)
  5. "KS B 6879:2020 – Heat recovery ventilators", ~
  6. Kyungjoo Cho, "Effect of Bypass Control and Room Control Modes on Fan Energy Savings in a Heat Recovery Ventilation System", Energies, 13(7), pp.1815~ (2020)
  7. Jaakkola JJ, "Sick building syndrome, sensation of dryness, and thermal comfort in relation to room temperature in an office building: Need for individual control of temperature", Environ Int, 15(1), pp.163~168 (1989)
  8. Yoonbeom Choi, "A Review of Health Effects of Indoor Thermal Environments", The Korean Journal of aerospace and environmental medicine, 21(2) (2011)