가속도에 민감한 종합병원 의료 및 기계설비의 내진성능평가
Seismic Performance Evaluation of Acceleration-sensitive Medical and Mechanical Equipments in General Hospitals
0
조회
0
다운로드
2
인용
0
참고문헌
키워드
초록
The main function of the general hospital building is to provide medical facilities and service. However, damage to the non-structural elements such as architectural, medical, mechanical and other components will interrupt those functions after the earthquake. Especially, it is considered that, damage to the non-structural elements is a serious event because it is directly associated with the lives of patients. Therefore, this study evaluated whether the certain non-structural elements of general hospital building has the seismic performance to provide hospital medical services after the earthquake. The evaluation is conducted by selecting the non-structural elements used in general hospital which are sensitive to acceleration, such as cooling towers, air handler, MRI and CT. As a result, the non-structural elements located on the upper floor without suitable support method did not meet the performance objective. Therefore, adequate anchorage against the seismic event is required for such non-structural elements that are acceleration-sensitives.
Abstract
The main function of the general hospital building is to provide medical facilities and service. However, damage to the non-structural elements such as architectural, medical, mechanical and other components will interrupt those functions after the earthquake. Especially, it is considered that, damage to the non-structural elements is a serious event because it is directly associated with the lives of patients. Therefore, this study evaluated whether the certain non-structural elements of general hospital building has the seismic performance to provide hospital medical services after the earthquake. The evaluation is conducted by selecting the non-structural elements used in general hospital which are sensitive to acceleration, such as cooling towers, air handler, MRI and CT. As a result, the non-structural elements located on the upper floor without suitable support method did not meet the performance objective. Therefore, adequate anchorage against the seismic event is required for such non-structural elements that are acceleration-sensitives.
참고문헌 (16)
- Pohang city hall, "11. 15 Eathquake damage investigation and damage control", Pohang City Disaster Safety Countermeasures Headquarters, ~ (2017)
- AIK, "KBC 2016. Korean building code-structural", code-structural, ~ (2016)
- ASCE, "Minimum design loads for buildings and other structures (ASCE", SEI 7-10), 2010
- Huang W, "A case study of performance-based seismic evaluation and retrofit of an existing hospital building in california, US", 14th World Conference on Earthquake Engineering (2008)
- "FEMA 577. Risk management series design guide for improving hospital safety in earhquakes, Floods, and High Winds", Federal Emergency Management Agency, ~ (2007)
- "California building code (california code of regulations, title 24). Part 1"[URL]
- "California building code (california code of regulations, title 24). Part 2, Volume 1"[URL]
- "California building code (california code of regulations, title 24). Part 2, Volume 2"[URL]
- Ministry of Health and Welfare, "Ministry of health and welfare notice No. 2016-201", ~
- 김남희, "우리나라 병원건축물의 내진성능향상을 위한 기초연구", 한국지진공학회논문집, 20(7), pp.509~516 (2016), 한국지진공학회
- ASCE, "Seismic evaluation and retrofit of existing buildings (ASCE", SEI 41-13), 2013
- Ministry of public safety and security, "Commentary of Seismic Design Code of Fire Facilities", ~ (2016)
- KCI, "KCI 2012. Concrete design code of Korea", Korea Concrete Institute, ~ (2012)
- Static friction in rubber-metal contacts with application to rubber pad forming processes, "Elena loredna Deladi", University of Twente, ~ (2006)
- 김태완, "중층 종합병원 건물의 내진성능평가", 한국지진공학회논문집, 21(5), pp.245~254 (2017), 한국지진공학회
- "PEER Strong Motion Database"[URL]