The building which are essential for disaster recovery is classified as a special seismic use group. Especially, achievement of seismic performance is very important for the hospital, so the hospital should be able to maintain its function during and right after an earthquake without significant damage on both structural and non-structural elements. Therefore, this study aimed at checking the seismic performance of a hospital building, but which was limited to structural elements. For the goal, a plan with a configuration of general hospitals in Korea was selected and designed by two different seismic-force-resisting systems. In analytical modeling, the shear behavior of the wall was represented by three inelastic properties as well as elastic. Nonlinear dynamic analyses were conducted to evaluate the performance of structural members. The result showed that the performance of shear walls in the hospital buildings was not satisfied regardless of the seismic-force-resisting systems, while the demands on the beams and columns did not exceed the capacities. This is the result of only considering the shear of the wall as the force-controlled action. When the shear of the wall was modeled as inelastic, the walls were yielded in shear, and as the result, the demands for frames were increased. However, the increase did not exceed the capacities of the frames members. Consequently, since the performance of walls is significant to determine the seismic performance of a hospital building, it will be essential to establish a definite method of modeling shear behavior of walls and judging their performance.

Abstract

The building which are essential for disaster recovery is classified as a special seismic use group. Especially, achievement of seismic performance is very important for the hospital, so the hospital should be able to maintain its function during and right after an earthquake without significant damage on both structural and non-structural elements. Therefore, this study aimed at checking the seismic performance of a hospital building, but which was limited to structural elements. For the goal, a plan with a configuration of general hospitals in Korea was selected and designed by two different seismic-force-resisting systems. In analytical modeling, the shear behavior of the wall was represented by three inelastic properties as well as elastic. Nonlinear dynamic analyses were conducted to evaluate the performance of structural members. The result showed that the performance of shear walls in the hospital buildings was not satisfied regardless of the seismic-force-resisting systems, while the demands on the beams and columns did not exceed the capacities. This is the result of only considering the shear of the wall as the force-controlled action. When the shear of the wall was modeled as inelastic, the walls were yielded in shear, and as the result, the demands for frames were increased. However, the increase did not exceed the capacities of the frames members. Consequently, since the performance of walls is significant to determine the seismic performance of a hospital building, it will be essential to establish a definite method of modeling shear behavior of walls and judging their performance.

참고문헌 (14)

  1. AIK, "KBC 2016. Korean building code-structural", Architectural Institute of Korea, ~ (2016)
  2. "California building Code (California Code of Regulations, Title 24). Part 1"[URL]
  3. "California building Code (California Code of Regulations, Title 24). Part 2, Volume 1"[URL]
  4. "California building Code (California Code of Regulations, Title 24). Part 2, Volume 2"[URL]
  5. Ministry of Health and Welfare, "Ministry of Health and Welfare notice No. 2016-201", ~
  6. Gilani ASJ, "Seismic Rehabilitation of a Nine-Story Hospital Building Using Fluid Viscous Dampers", Structures Congress 2006 : Structural Engineering and Public Safety (2006)
  7. Chen XW, "Seismic perf ormance analysis o f wenchuan hospital structure with viscous dampers", The Structural Design of Tall and Special Buildings, 19(4), pp.397~419 (2010)
  8. MIDAS GEN, "MIDAS GEN - User Manual. ver 860", MIDAS IT, ~ (2017)
  9. CSI, "Perform-3D, Nonlinear analysis and performance assessment for 3D sturctures, user guide version 5", Computers and Structures Inc, ~ (2011)
  10. AIK, "Guidelines for performance-based seismic design of residential buildings", 13~33 (2016)
  11. ASCE, "Seismic evaluation and retrofit of existing buildings (ASCE", SEI 41-13), 2013
  12. KCI, "Building Code Requirements for Structural Concrete (KCI2012)", Korea Concrete Institute, ~ (2012)
  13. "ATC-72-1, Modeling and acceptance criteria for seismic design and analysis of tall buildings", Pacific Earthquake Engineering Research Center, ~ (2010)
  14. "PEER Strong Motion Database"[URL]