본문 바로가기
KERD
논문KCI 등재

저에너지주택내 지중순환수 조건 변화에 따른 지열 히트펌프의 동절기 성능평가

The Performance of Ground Source Heat Pump System for Domestic Heating under various Ground Water Circulation Conditions

0

조회

0

다운로드

1

인용

0

참고문헌

키워드

초록

This study is evaluates the performance of a prototype ground source heat pump(GSHP) system under various secondary fluid flow rates. The prototype GSHP has four functions : space heating, cooling, floor heating and domestic water heating. Heating can be operated by two operational modes : water to water and water to air. As a result, the COP of GSHP was increased from 3.43 to 3.84 when the underground circulation flow rate was increased, but ratio of increased in COP was decreased. When the flow rate of the GSHP system including electricity consumption of the ground circulation pump was increased 19.2 LPM to 47.4 LPM, the COP was increased by up to 6.1%, but flow rate was increased 47.4 to 87.7 LPM, the COP was decreased by up to 6.2%. It is suggested that the GSHP with an underground circulation inverter pump saves power consumption in the operation mode, a variable-speed control of ground circulation flow rate based on a compressor Hz have to be selected in order to optimize COP of GSHP system.

Abstract

This study is evaluates the performance of a prototype ground source heat pump(GSHP) system under various secondary fluid flow rates. The prototype GSHP has four functions : space heating, cooling, floor heating and domestic water heating. Heating can be operated by two operational modes : water to water and water to air. As a result, the COP of GSHP was increased from 3.43 to 3.84 when the underground circulation flow rate was increased, but ratio of increased in COP was decreased. When the flow rate of the GSHP system including electricity consumption of the ground circulation pump was increased 19.2 LPM to 47.4 LPM, the COP was increased by up to 6.1%, but flow rate was increased 47.4 to 87.7 LPM, the COP was decreased by up to 6.2%. It is suggested that the GSHP with an underground circulation inverter pump saves power consumption in the operation mode, a variable-speed control of ground circulation flow rate based on a compressor Hz have to be selected in order to optimize COP of GSHP system.

참고문헌 (10)

  1. Ground-source heat pumps applied to federal facilities second edition, "DOE", Federal Energy Management Program, ~, pp.DOE (2001), EE-0245(PNNL-13534)
  2. Ozgener, L., "A key review on performance improvement aspects of geothermal district heating systems and applications", Renew Sustainable Energy Rev, 11, pp.1675~1697 (2007)
  3. 에너지관리공단, "2013년 신・재생에너지 보급통계", 에너지관리공단 신・재생에너지센터, 50~51 (2014)
  4. X. Q. Zhai., "Experimental investigation and optimization of a ground source heat pump system under different indoor set temperatures", Applied Thermal Engineering, 48, pp.105~116 (2012)
  5. Michopoulos, A., "Three-years operation experience of a ground source heat pump system in Northern Greece", Journal of Energy and Buildings, 39, pp.328~334 (2007)
  6. 손병후, "단독주택 적용 지열 히트펌프 시스템의 성능 분석", 설비공학 논문집, 23(6), pp.392~399 (2011), 대한설비공학회
  7. 이준엽, "지중 순환수 유량 변화에 따른 지열원 히트펌프 시스템의 성능 특성 연구", 설비공학 논문집, 22(10), pp.649~656 (2010), 대한설비공학회
  8. Euiyoung, Kim., "Performance evaluation under the actual operating condition of a vertical ground source heat pump system in a school building", Journal of Energy and Buildings, 50, pp.1~6 (2012)
  9. 최종민, "지열원 물대공기 멀티 히트펌프의 일일 난방 운전 특성에 관한 실증 연구", 설비공학 논문집, 21(9), pp.527~535 (2009), 대한설비공학회
  10. Suwon, Song, "An Experimental Study on Variablespeed Control of a Ground-water Circulation Pump Using Inlet and Outlet Water", Proceedings of the SAREK 2012 Summer Annual Conference, pp.179~182 (2012)

관련 논문AI추천