입자 균등성 확보를 위한 시험 챔버의 유동 시뮬레이션 및 이를 이용한 기상 부유균 저감 특성의 실험적 연구

Flow Simulation of Chamber System to Obtain Particle Uniformity and Study on Bio-aerosol Reduction Test

2

조회

0

다운로드

0

인용

0

참고문헌

키워드

초록

Since airborne bacteria have been known to aggravate indoor air quality, studies on reducing bacteria particles increase recently. In this study, a chamber(0.8m x 0.8m x 1.56m) system was built in order to simulate real conditions for reducing airborne bacteria, and evaluated by a simple aerosol reduction test. A method utilizing CFD(Computational Fluid Dynamics) simulation was used to detect the horizontal cross-sectional area which represents particle distribution in the chamber. Then an air-cleaner with HEPA filter and Carbon Fiber Ionizer was located on that area for aerosol reduction test. The CFD result found the area was located at 0.2m height from the bottom of the chamber, and the test showed aerosol reduction efficiencies using measurements of number concentration and CFU(colony forming unit) per each case. At the measurement of number concentration, the reduction efficiency of air-cleaner with filter and ionizer(Case 3) was about 90% after 4 minutes from the stop of the bacteria injection, and that with only filter(Case 2) was about 90% after 8 minutes from the beginning. Lastly, that without filter and ionizer(Case 1) was about 30% after 10 minutes. At the measurement of CFU, it shows similar results but it is related to viability of bio-aerosol.

Abstract

Since airborne bacteria have been known to aggravate indoor air quality, studies on reducing bacteria particles increase recently. In this study, a chamber(0.8m x 0.8m x 1.56m) system was built in order to simulate real conditions for reducing airborne bacteria, and evaluated by a simple aerosol reduction test. A method utilizing CFD(Computational Fluid Dynamics) simulation was used to detect the horizontal cross-sectional area which represents particle distribution in the chamber. Then an air-cleaner with HEPA filter and Carbon Fiber Ionizer was located on that area for aerosol reduction test. The CFD result found the area was located at 0.2m height from the bottom of the chamber, and the test showed aerosol reduction efficiencies using measurements of number concentration and CFU(colony forming unit) per each case. At the measurement of number concentration, the reduction efficiency of air-cleaner with filter and ionizer(Case 3) was about 90% after 4 minutes from the stop of the bacteria injection, and that with only filter(Case 2) was about 90% after 8 minutes from the beginning. Lastly, that without filter and ionizer(Case 1) was about 30% after 10 minutes. At the measurement of CFU, it shows similar results but it is related to viability of bio-aerosol.

참고문헌 (6)

  1. Fischer, G., "Species-specific production of microbial volatile organic compounds(MVOC)by airborne fungi from a compost facility", Chemosphere, 39(5), pp.795~810 (1999)
  2. 홍성갑, "에어컨내 세균의 분리, 동정 및 위생", 미생물학회지, 39(4), pp.283~287 (2003), 한국미생물학회
  3. 김두영, "상용 소형 에어컨의 항균성능 향상을 위한 탄소섬유 이오나이저의 적용", 한국실내환경학회지, 7(2), pp.77~88 (2010), 한국실내환경학회
  4. Kim, Y. S., "Health effect of indoor air pollution", SAREK Magazine and ASHRAE Journal, 24(1), pp.29~32 (1995)
  5. Menetrez, M. Y., "Microbial volatile organic compound emission rates and exposure model", Indoor and Built Environment, 11(4), pp.208~213 (2002)
  6. 윤기영, "상용 항균 필터 여재의 바이오에어로졸 저감 특성", 한국실내환경학회지, 5(4), pp.329~337 (2008), 한국실내환경학회