Detection and localization of partial discharge are considered critical techniques for estimating the lifetimes of power cables. Highfrequency current transformers (HFCTs) are commonly used for the detection of partial discharge in high-voltage alternating current (HVAC) power cables; however, their applicability is compromised by the limitations of the installation locations. HFCTs are typically installed in cable terminals or insulation joint boxes because HVACs induce strong time-varying magnetic fields around the cables, saturating the ferromagnetic materials in the HFCTs. Therefore, partial discharges near the installation locations can be detected. In this study, the feasibility of partial discharge detection using a HFCT was investigated for high-voltage direct current (HVDC) cables. We demonstrated that the HFCT could be installed at any location in the HVDC power cable to monitor partial discharge along the entire cable length. Furthermore, we showed that the HFCT could detect the location of partial discharge with high accuracy.

Abstract

Detection and localization of partial discharge are considered critical techniques for estimating the lifetimes of power cables. Highfrequency current transformers (HFCTs) are commonly used for the detection of partial discharge in high-voltage alternating current (HVAC) power cables; however, their applicability is compromised by the limitations of the installation locations. HFCTs are typically installed in cable terminals or insulation joint boxes because HVACs induce strong time-varying magnetic fields around the cables, saturating the ferromagnetic materials in the HFCTs. Therefore, partial discharges near the installation locations can be detected. In this study, the feasibility of partial discharge detection using a HFCT was investigated for high-voltage direct current (HVDC) cables. We demonstrated that the HFCT could be installed at any location in the HVDC power cable to monitor partial discharge along the entire cable length. Furthermore, we showed that the HFCT could detect the location of partial discharge with high accuracy.

참고문헌 (10)

  1. I.E.C. Standard, "High Voltage Test Techniques: Partial discharge Measurement, IEC-60270", 13~31 (2000)
  2. P. A. A. F. Wouters, "New on-line PD measurement technique for polymer insulated cables and accessories", Proc of 8th Int. Symp. on High Voltage Engineering, pp.105~108 (1993)
  3. N. H. Ahmed, "On-line partial discharge detection in cables", IEEE-DEI Trans., 5(2), pp.181~188 (1998)
  4. B. T. Phung, "Online partial discharge measurement on high voltage power cables", Proc. of 11th Int. Symp. on High Voltage Engineering, pp.328~332 (1999)
  5. Z. Liu, "The propagation of partial discharge pulses in a HV cable", Proc. of AUPEC, 1999, 287~292
  6. E. F. Steennis, "Learning from high-voltage XLPE cable system testing and monitoring", CIGRE, 21~203 (2000)
  7. W. Wei, "The study of online PD detector in power cable", Proc. of 6th Int. Conf. on Properties and Applications of Dielectric Materials, pp.177~180 (2000)
  8. A. Rodrigo, "Influence of High Frequency Current Transformers Bandwidth on Charge Evaluation in Partial Discharge Measurements", IEEE Trans. Dielectr. Electr. Insul., 18(5), pp.1798~1802 (2011)
  9. A. Rodrigo, "Study of Partial Discharge Charge Evaluation and the Associated Uncertainty by Means of High Frequency Current Transformers", IEEE Trans. Dielectr. Electr. Insul., 19(2), pp.434~442 (2012)
  10. D. Jovcic, "High voltage direct current transmission: Converters, Systems and DC Grids", pp.1~12 (2019), John Wiley &Sons