In this study, the solar chimney, one of the passive solar systems, is proposed as a method to improve the thermal environment of northern zones in buildings. As this well-known system has rarely been used in building projects, an adequate application of the system is proposed in this paper: the solar chimney system is designed to meet the required ventilation rate and consequently to reduce the ventilation load in the northern part of a building. To investigate such a possibility, a numerical model for the system is developed, and results of numerical tests are used for energy simulations. The results were taken into account for test simulations in EnergyPlus. As a result, approximately 75% of the volumetric ventilation rate required in the north zone could be supplied with the air volume acquired through the system and the monthly mean load was reduced by 29.5%, from 1.584 kWh to 1.117 kWh. The analyses of hourly mean heating and ventilation load over the heating period indicated that the system was very effective at around 13:00. Results show that 33% reduction in the ventilation load and 17% in the heating load for the north zone could be acquired through this system.
Abstract
In this study, the solar chimney, one of the passive solar systems, is proposed as a method to improve the thermal environment of northern zones in buildings. As this well-known system has rarely been used in building projects, an adequate application of the system is proposed in this paper: the solar chimney system is designed to meet the required ventilation rate and consequently to reduce the ventilation load in the northern part of a building. To investigate such a possibility, a numerical model for the system is developed, and results of numerical tests are used for energy simulations. The results were taken into account for test simulations in EnergyPlus. As a result, approximately 75% of the volumetric ventilation rate required in the north zone could be supplied with the air volume acquired through the system and the monthly mean load was reduced by 29.5%, from 1.584 kWh to 1.117 kWh. The analyses of hourly mean heating and ventilation load over the heating period indicated that the system was very effective at around 13:00. Results show that 33% reduction in the ventilation load and 17% in the heating load for the north zone could be acquired through this system.
참고문헌 (15)
- 장향인, "지하공간의 자연환기를 위한 태양 굴뚝 시스템의 응용", 한국태양에너지학회 논문집, 30(2), pp.87~95 (2010), 한국태양에너지학회
- Mathur. J, "Experimental investigations on solar chimney for room ventilation", Solar Energy, 80(8), pp.927~935 (2006)
- Miyazaki. T, "The effect of solar chimneys on thermal load mitigation of office buildings under the Japanese climate", Renewable Energy, 31(7), pp.987~1010 (2006)
- Final Report on Building Energy Intensity Basis Study, "Ministry of Commerce, Industry and Energy", 130~139 (1999)
- ASHRAE, "ASHRAE Handbook Fundamentals, American Society of Heating", pp.172~174 (2009), Refrigerating and Air-Conditioning Engineers, Inc
- ASHRAE Standard 62.1 Ventilation for Acceptable Indoor Air Quality, American Society of Heating, "ANSI", pp.2007, ASHRAE
- Ong. K. S, "Performance of solar chimney", Solar Energy, 74(1), pp.1~7 (2003)
- Suh. S. J, "Thermal Environment in Building based on Theory and Analysis", pp.280~ (2009), Iljinsa
- Trombe. F, "Concrete Walls to Collect and Hold Heat", Solar Age, 2(8), pp.13~19 (1977)
- Watmuff. J. H, "Solar and Wind induced External Coefficients for Solar Collectors" (1977), Revue Internationale d'Heliotechnique
- Churchill. S, "Correlating Equations for Laminar and Turbulent Free Convection from a Horizontal Cylinder", International Journal of Heat Mass Transfer, 18(9), pp.1049~ (1975)
- Architectural Institute of Korea, "Construction environmental planning", pp.78~ (2003), Kimoondang
- Swinbank. W. C, "Long-wave radiation from clear skies", QJR Meteorological Society, 89(381), pp.339~348 (1963)
- Suh. S. J, "Environmental Engineering in Architecture", pp.40~ (2004), Iljinsa
- "EnergyPlus Documentation, EnergyPlus Manual, Version 8.1", Department of Energy, ~ (2013)