This study aims to analyze the performance of solar thermal system with heat pump for domestic hot water and heat supply. There are four types of system. Systems are categorized based on the existence of a heat pump and the ways of controlling the working fluid circulating from the collector. Working fluid is controlled by either temperature level (categorized as system 1 and 2) or sequential flow (system 3 and 4). Heat balance of the system, the solar fraction, hot water and heating supply rates, and performance of heat pump are analyzed using TRNSYS and TESS component programs. Technical specifications of the main facilities are as follow; the area of the collector to 25 ㎡, the volumes of the main tank and the buffer tank to 0.5㎥ and 0.8 ㎥, respectively. Heating capacity of the heat pump in the heating mode is set to 30,000 kJ / hr. Hot water supply set 65 liters per person each day, total heat transfer coefficient of the building to 1,500 kJ / kg.K. Indoor temperature is kept steadily around 22℃. The results are as follows; 6 months average solar fraction of system 1 turns out to be 39%, which is 6.7% higher than system 2 without the heat pump, indicating a 25% increase of solar fraction compared to that of system 2. In addition, the solar fraction of system 1 is 2% higher than that of system 3. Hot water and heating supply rate of system 1 are 93% and 35%, respectively. Considering the heat balance of the system, higher heat efficiency, and solar fraction, as whole, it can be concluded that system 1 is the most suitable system for hot water and heat supply.
Abstract
This study aims to analyze the performance of solar thermal system with heat pump for domestic hot water and heat supply. There are four types of system. Systems are categorized based on the existence of a heat pump and the ways of controlling the working fluid circulating from the collector. Working fluid is controlled by either temperature level (categorized as system 1 and 2) or sequential flow (system 3 and 4). Heat balance of the system, the solar fraction, hot water and heating supply rates, and performance of heat pump are analyzed using TRNSYS and TESS component programs. Technical specifications of the main facilities are as follow; the area of the collector to 25 ㎡, the volumes of the main tank and the buffer tank to 0.5㎥ and 0.8 ㎥, respectively. Heating capacity of the heat pump in the heating mode is set to 30,000 kJ / hr. Hot water supply set 65 liters per person each day, total heat transfer coefficient of the building to 1,500 kJ / kg.K. Indoor temperature is kept steadily around 22℃. The results are as follows; 6 months average solar fraction of system 1 turns out to be 39%, which is 6.7% higher than system 2 without the heat pump, indicating a 25% increase of solar fraction compared to that of system 2. In addition, the solar fraction of system 1 is 2% higher than that of system 3. Hot water and heating supply rate of system 1 are 93% and 35%, respectively. Considering the heat balance of the system, higher heat efficiency, and solar fraction, as whole, it can be concluded that system 1 is the most suitable system for hot water and heat supply.
참고문헌 (8)
- 박재완, "그린홈 공동주택의 최적 에너지 공급시스템 설계를 위한 부하 예측 연구", 한국태양에너지학회 논문집, 33(1), pp.24~31 (2013), 한국태양에너지학회
- 한유리, "태양열 온수 및 난방 일체형 복합시스템의 성능예측", 한국태양에너지학회 논문집, 32(5), pp.12~17 (2012), 한국태양에너지학회
- 백남춘, "콤팩트형 태양열", 지열히트펌프 하이브리드 냉난방 및 급탕 시스템 개발 및 성능분석, 2012, pp.32(5), 59~67[DOI]
- 남유진, "태양열 및 지열 이용 히트펌프 시스템의 성능예측시뮬레이션에 관한 연구", 한국태양에너지학회 논문집, 34(3), pp.75~81 (2014), 한국태양에너지학회
- 이동원, "자연형 및 설비형 태양열 온수기의집열특성에 대한 실험적 연구", 한국태양에너지학회 논문집, 33(6), pp.12~18 (2013), 한국태양에너지학회
- Sterling, S. J., "Feasibility Analysis of an Indirect Heat Pump Assisted Solar Domestic Hot Water System", Applied Energy, 93, pp.11~18 (2012)
- Barnister, C. J., "Development and Performance of a Dual Tank Solar-assisted Heat Pump System", Applied Energy, 149, pp.125~132 (2015)
- A Review of Hot Water Draw Porfiles Used in Performance Analysis of Residential Domestic Hot Water Systems, "Philip. F", Florida Solar Energy Center, ~, pp.Publication No. FSEC-RR-56-04 (2004)