본문 바로가기
KERD
논문KCI 등재

태양열급탕시스템의 집열기 배열에 따른 에너지성능 분석 및 평가

Analysis on the Energy Performance of Solar Water Heating System according to the Configuration of Flat Plate Collectors

2

조회

0

다운로드

1

인용

0

참고문헌

키워드

주제분류기타공학

초록

The objective of this work is to analyze the variation in energy performance for each flat plate collector connected in series. In this study, it was assumed that solar water heating system with annual solar fraction of 60% was installed in an office building in Seoul, South Korea. The transient energy performance corresponding to four cases, which are selected using different solar radiation and outdoor air temperature, is studied by analyzing the variation in outlet temperature, solar useful heat gain, and thermal efficiency of each collector. It is observed that the useful heat gain and the collector efficiency decrease continuously, and outlet temperature increases when increasing the number of collector connected in series. The long-term performance is assessed by evaluating the thermal efficiency of each collector for two solar radiation conditions ranging from 780 to 820 W/㎡ and from 380 to 420 W/㎡. It is found that the differences between the intercept and slope of the efficiency curves for first and eighth collectors are 3.68% and 6.74% for solar radiation of 800 ± 20 W/㎡ and 8.57% and 12.90% for solar radiation of 400 ± 20 W/㎡, respectively. In addition, it is interesting to note that annual useful heat gain and collector efficiency are reduced with similar rate of about 6.13% when increasing the collector area by connecting the collectors in series.

Abstract

The objective of this work is to analyze the variation in energy performance for each flat plate collector connected in series. In this study, it was assumed that solar water heating system with annual solar fraction of 60% was installed in an office building in Seoul, South Korea. The transient energy performance corresponding to four cases, which are selected using different solar radiation and outdoor air temperature, is studied by analyzing the variation in outlet temperature, solar useful heat gain, and thermal efficiency of each collector. It is observed that the useful heat gain and the collector efficiency decrease continuously, and outlet temperature increases when increasing the number of collector connected in series. The long-term performance is assessed by evaluating the thermal efficiency of each collector for two solar radiation conditions ranging from 780 to 820 W/㎡ and from 380 to 420 W/㎡. It is found that the differences between the intercept and slope of the efficiency curves for first and eighth collectors are 3.68% and 6.74% for solar radiation of 800 ± 20 W/㎡ and 8.57% and 12.90% for solar radiation of 400 ± 20 W/㎡, respectively. In addition, it is interesting to note that annual useful heat gain and collector efficiency are reduced with similar rate of about 6.13% when increasing the collector area by connecting the collectors in series.

참고문헌 (7)

  1. Wang, Z., "Solar water heating: From theory, application, marketing and research", Renewable and Sustainable Energy Reviews, 41, pp.68~84 (2015)
  2. Lim, B. M., "Energy performance analysis of solar water heating system according to the configuration of flat plate collectors using TRNSYS simulation", Korean Society of Living Environmental System Autumn Conference Proceedings, pp.51~54 (2015)
  3. Garg, H. P., "Design and performance of a large-sized solar water heater", Solar Energy, 14, pp.303~312 (1973)
  4. Morrison, G. L., "Solar Energy-The State of the Art-ISES Position Papers", pp.145~221 (2001), James and James Science Publishers
  5. Luminosu, I., "Determination of the optimal operation mode of a flat solar collector by exergetic analysis and numerical simulation", Energy, 30(5), pp.731~747 (2005)
  6. Duffie, J. A., "Solar engineering of thermal processes" (2006), Wiley
  7. "U.S. department of energy commercial reference building models of the national building stock"[URL]