난연 처리된 실내장식섬유의 연기 위해성 증가에 관한 연구 -비스코스 레이온 섬유 벽지를 중심으로-
A Study on the Smoke Hazard Increase of Flame-retardant-treated Interior Decorative Textile -Focused on Viscose Rayon Textile Wallcovering-
0
조회
0
다운로드
0
인용
0
참고문헌
키워드
초록
This study was conducted to identify problems in domestic flame-retardant performance specifications. Currently, the domestic wallcovering anti-inflammatory regulations are not prepared for damage caused by smoke, with the carbonized area as the main function. In particular, given that smoke is the main cause of human casualties and injuries in a fire, it is reasonable that the flame density and toxicity of the wallcovering should also be the main performance indicators. The scope and method of research in this study were as follows. First, a prior study related to fire on various wallcoverings was considered. Second, it raised questions about the effects of smoke in the event of a fire and domestic anti-inflammatory performance tests. Third, textile wallcovering samples were manufactured with viscose rayon for experimental verification of the problems and tested by Korean and EU standards without flame retardant processing to analyze the differences between each regulation. Fourth, the performance of flame retardant wallcovering according to Korean standards was evaluated using smoke density and harmful gas testing methods. The results of each test were as follows. Non-fire retardant wallcovering was rejected by Korea standards. However, B-s1.d0 in Europe. Smoke density testing and harmful gas by domestic combustion processing on the same sample showed that the smoke density increased about 4.3 times more than before, and the harmful gas test showed that the suspension of the post-processing sample slowed earlier than the non-processed sample.
Abstract
This study was conducted to identify problems in domestic flame-retardant performance specifications. Currently, the domestic wallcovering anti-inflammatory regulations are not prepared for damage caused by smoke, with the carbonized area as the main function. In particular, given that smoke is the main cause of human casualties and injuries in a fire, it is reasonable that the flame density and toxicity of the wallcovering should also be the main performance indicators. The scope and method of research in this study were as follows. First, a prior study related to fire on various wallcoverings was considered. Second, it raised questions about the effects of smoke in the event of a fire and domestic anti-inflammatory performance tests. Third, textile wallcovering samples were manufactured with viscose rayon for experimental verification of the problems and tested by Korean and EU standards without flame retardant processing to analyze the differences between each regulation. Fourth, the performance of flame retardant wallcovering according to Korean standards was evaluated using smoke density and harmful gas testing methods. The results of each test were as follows. Non-fire retardant wallcovering was rejected by Korea standards. However, B-s1.d0 in Europe. Smoke density testing and harmful gas by domestic combustion processing on the same sample showed that the smoke density increased about 4.3 times more than before, and the harmful gas test showed that the suspension of the post-processing sample slowed earlier than the non-processed sample.
참고문헌 (13)
- 안영무, "침장용 난연 자카드직물의 제직설계", 패션 비즈니스, 14(5), pp.102~111 (2010), 한국패션비즈니스학회
- 조광현, "콘칼로리미터와 FTIR을 이용한 실내장식물의 연소특성에 관한 연구", 석사, 방재공학, pp.2009
- Ju, J., "A study on the variation of flame-resistance performance with temperature rise of flame-resistance treated plywood", master, pp.2017
- "KFI", 2001
- "Journal of Korean Society for Railway", 2005, 58~66
- "KS", 2017
- "1974", 3
- 이준한, "반응성염료를 이용한 스트링벽지 패딩염색에 관한 연구", 패션 비즈니스, 21(2), pp.105~112 (2017), 한국패션비즈니스학회[DOI]
- Park, M., "A study on total fire risk assessment for wallpaper", master, pp.2003
- Park, S., "A study on carbonization pattern of wallpaper according to the hydrothermal temperature of walls", Proceeding of 2017Autumn Conference on Fire Science and Engineering, pp.9~10 (2017), Korean Institute of Fire Science &Engineering
- Park, Y., "A study on fire risk assessment of fire retardant paint", Proceeding of 2004 Summer Conference on Fire Science and Engineering, pp.15~19 (2004), Korean Institute of Fire Science & Engineering
- 신정화, "난연가공 처리된 섬유제품중의 유해무기화합물 분석", 한국생활환경학회지, 15(4), pp.454~458 (2008), 한국생활환경학회
- 원동빈, "방염물질의 화재시 가스유해성 평가 및 예측모델 연구", 석사, 화학공학, pp.2008