Coal tar-coated pipes buried in a domestic nuclear power plant have operated under the cathodic protection. This work conducted the simulation of the coating performance of these pipes using a FEM method. Thepipes, being ductile cast iron have been suffered under considerably high cathodic protection condition beyondthe appropriate condition. However, cathodic potential measured at the site revealed non-protected status. Converting from 3D CAD data of the power plant to appropriate type for a FEM simulation was conductedand cathodic potential under the applied voltage and current was calculated using primary and secondarycurrent distribution and physical conditions. FEM simulation for coal tar-coated pipe without defects revealedover-protection condition if the pipes were well-coated. However, the simulation for coal tar-coated pipeswith many defects predict that the coated pipes may be severely degraded. Therefore, for high risk pipes,direct examination and repair or renewal of pipes are strongly recommended.

Abstract

Coal tar-coated pipes buried in a domestic nuclear power plant have operated under the cathodic protection. This work conducted the simulation of the coating performance of these pipes using a FEM method. Thepipes, being ductile cast iron have been suffered under considerably high cathodic protection condition beyondthe appropriate condition. However, cathodic potential measured at the site revealed non-protected status. Converting from 3D CAD data of the power plant to appropriate type for a FEM simulation was conductedand cathodic potential under the applied voltage and current was calculated using primary and secondarycurrent distribution and physical conditions. FEM simulation for coal tar-coated pipe without defects revealedover-protection condition if the pipes were well-coated. However, the simulation for coal tar-coated pipeswith many defects predict that the coated pipes may be severely degraded. Therefore, for high risk pipes,direct examination and repair or renewal of pipes are strongly recommended.

참고문헌 (14)

  1. "EPRI 1016456, Recommendations for an Effective Program to Control the Degradation of Buried and Underground Piping and Tanks, Revision 1", ~ (2010)
  2. Development of corrosion environment survey and analysis method for buried pipe (II), "KISTEK", ~ (1999)
  3. KOGAS, "Protection technique handbook", pp.18~ (2003)
  4. "EPRI 1022962, Plant Engineering: Evaluation of Indirect Assessment Techniques for Coating Flaw Detection", ~ (2011)
  5. "NUREG-1801, Generic Aging Lessons Learned (GALL)Report, Revision 2", USNRC, Dec, ~ (2010)
  6. "License Renewal Interim Staff Guidance, Changes to Buried and Underground Piping and Tank Recommendations, LR-ISG-2015-01", USNRC, ~ (2015)
  7. B. Allik, "U.S. NRC Update on Buried and Underground Piping and Tanks", BPIG-CPUG Meeting (2016), EPRI
  8. W. C. Holston, "Changes to Buried and Underground Piping and Tank Recommendations", BPIG Meeting (2015), EPRI
  9. "Act No. 13616, Nuclear Safety Act, Article 20 and 21, Periodic Safety review", ~ (2017)
  10. "ML16041A090, Selective Leaching of Ductile Iron for GALL-SLR(Generic Aging Lessons Learned-Subsequent License Renewal)", USNRC, ~ (2015)
  11. 김기태, "REAL-TIME CORROSION CONTROL SYSTEM FOR CATHODIC PROTECTION OF BURIED PIPES FOR NUCLEAR POWER PLANT", CORROSION SCIENCE AND TECHNOLOGY, 14(1), pp.12~18 (2015), 한국부식방식학회[DOI]
  12. H. Y. Chang, , KPVP, 11, pp.61~ (2015)
  13. "COMSOL™, Guidebook of COMSOLTM Multiphysics (Chemistry-Electrochemistry)", ALTSOFT, ~ (2014)
  14. M. Tabatabaian, "COMSOLTM for Engineers", Mercury Learning and Information, ~ (2014)