REAL-TIME CORROSION CONTROL SYSTEM FOR CATHODIC PROTECTION OF BURIED PIPES FOR NUCLEAR POWER PLANT
0
조회
0
다운로드
4
인용
0
참고문헌
키워드
초록
Since the operation period of nuclear power plants has increased, the degradation of buried pipes graduallyincreases and recently it seems to be one of the emerging issues. Maintenance on buried pipes needs highquality of management system because outer surface of buried pipe contacts the various soils but innersurface reacts with various electrolytes of fluid. In the USA, USNRC and EPRI have tried to manage thedegradation of buried pipes. However, there is little knowledge about the inspection procedure, test andmanage program in the domestic nuclear power plants. This paper focuses on the development and build-upof real-time monitoring and control system of buried pipes. Pipes to be tested are tape-coated carbon steelpipe for primary component cooling water system, asphalt-coated cast iron pipe for fire protection system,and pre-stressed concrete cylinder pipe for sea water cooling system. A control system for cathodic protectionwas installed on each test pipe which has been monitored and controlled. For the calculation of protectionrange and optimization, computer simulation was performed using COMSOL Multiphysics (Altsoft co.).
Abstract
Since the operation period of nuclear power plants has increased, the degradation of buried pipes graduallyincreases and recently it seems to be one of the emerging issues. Maintenance on buried pipes needs highquality of management system because outer surface of buried pipe contacts the various soils but innersurface reacts with various electrolytes of fluid. In the USA, USNRC and EPRI have tried to manage thedegradation of buried pipes. However, there is little knowledge about the inspection procedure, test andmanage program in the domestic nuclear power plants. This paper focuses on the development and build-upof real-time monitoring and control system of buried pipes. Pipes to be tested are tape-coated carbon steelpipe for primary component cooling water system, asphalt-coated cast iron pipe for fire protection system,and pre-stressed concrete cylinder pipe for sea water cooling system. A control system for cathodic protectionwas installed on each test pipe which has been monitored and controlled. For the calculation of protectionrange and optimization, computer simulation was performed using COMSOL Multiphysics (Altsoft co.).
참고문헌 (14)
- "Inspection Procedure 62002, Inspection of Structures, Passive Components, and Civil Engineering Features at Nuclear Power Plants", USNRC, ~ (1996)
- Recommendations for an Effective Program to Control the Degradation of Buried and Underground Piping and Tanks, , EPRI, ~, pp.EPRI-1016456 (2010)
- Nondestructive Evaluation: Buried Pipe Nondestructive Evaluation Reference Guide Rev. 1, , EPRI, ~, pp.EPRI-1021626 (2011)
- Buried Pipe Guided Wave Examination Reference Document, , EPRI, ~, pp.EPRI-1019115 (2009)
- Nondestructive Evaluation : Guided Wave Technology Development and Nuclear Application Assessment, , EPRI, ~, pp.EPRI-1015156 (2007)
- Condition Assessment of Large- Diameter Buried Piping: Phase 1-Feasibility, , EPRI, ~, pp.EPRI-1008186 (2004)
- Condition Assessment of Large- Diameter Buried Piping: Phase 2-Vehicle Design and Construction, , EPRI, ~, pp.EPRI-1011829 (2005)
- Condition Assessment of Large- Diameter Buried Piping: Phase 3-Field Trial, , EPRI, ~, pp.EPRI-1013468 (2006)
- "Buried Piping and Raw Water Corrosion Program (BPRWCP) Guide", Excelon Nuclear
- Y. S. Kim, , Corros. Sci. Tech, 31, pp.70~ (2002)
- H.Y.Chang, "A Study on the Coatings for CP System in the Environment in which Thin Layer of Extremely Acidic Fluids are Formed", CORROSION SCIENCE AND TECHNOLOGY, 5(1), pp.5~14 (2006), 한국부식방식학회
- "NACE Standard RP0100, Cathodic protection of pre-stressed concrete cylinder pipelines", ~
- "NACE Standard RP0575, Internal cathodic protection systems in oil-treating vessels", ~
- "ASTM G4, Standard guide for conducting corrosion tests in field applications", ~