초록
This case covers the issues related to the operation problem, cause analysis and improvement cases of the FGD that employed the non-leakage type GGH in coal-fired power plant for the first time in Korea. In the Cooler, there was a main problem that the tube is damaged by the ash cutting due to the high velocity of flue gas in the duct and by the weak wear resistance of material. In the Reheater, there was a main problem that the tube was corroded due to chlorine and sulfur in the circumstance of the low temperature. In order to solve those problems, we have improved the Reheater tube and tube fins by coating enamel to reduce corrosion rate.
Abstract
This case covers the issues related to the operation problem, cause analysis and improvement cases of the FGD that employed the non-leakage type GGH in coal-fired power plant for the first time in Korea. In the Cooler, there was a main problem that the tube is damaged by the ash cutting due to the high velocity of flue gas in the duct and by the weak wear resistance of material. In the Reheater, there was a main problem that the tube was corroded due to chlorine and sulfur in the circumstance of the low temperature. In order to solve those problems, we have improved the Reheater tube and tube fins by coating enamel to reduce corrosion rate.
참고문헌 (12)
- Environmental Impact and Economic Analysis for Expanding Young-Heung Power Plants, "Kang KK", Korea Environment Institute, 18~19 (2012)
- Practice of Atmospheric Environment, "Lee JO", Korea Power Learning Institute, 88~89 (2016)
- Practice of FGD Management, "Lee JO", Korea Power Learning Institute, 10~62 (2016)
- Optimization of 500MW KEPAR De-SOx technology, "Ministry of Environment", Korea Electric Power Research Institute, 172~191 (2004)
- Research of improvement of FGD and SCR of Yeongheung power plant #1~4, "KC Cottrell", Korea South-East Power Company, 1~135 (2012)
- Practice of Fuel Management, "Lee JO", Korea Power Learning Institute, 10~62 (2016)
- Plan of Improving the FGD Non-leakage type GGH of Yeongheung Power Plant #3,4, "Seo YM", 1~18, pp.Internal Rep.YK(Turbine)-46704 (2012)
- Jeong HR, "Case Study for improving the reliability of FGD", Internal Presentation slide, 1~23 (2017)