동관에서 pH, 알칼리도, 염소이온이 부식에 미치는 영향
The effect of pH, Alkalinity, Chloride ion on the Corrosion in the Copper Pipe
1
조회
0
다운로드
7
인용
0
참고문헌
초록
Abstract
This study investigated the effects of pH, alkalinity, and chlorine ion which are important water quality impact factors to the corrosion in the simulated distribution system where the copper pipe is affixed. The result shows that pitting index was increased as the alkalinity and chloride ion increase in the distilled water, but there was no relation to pH. Actually the uniform corrosion rate was decreased as the pH increase with the laboratory tap water. In conclusion, it is necessary to control the pH which stands above minimum 7.5 to prevent pitting corrosion in the copper pipe. Consequently, comprehensive research about the effect of lime soda (Ca(OH)2) which was used as a coagulation additive in the water treatment plant to pipe corrosion must be accomplished additionally.
참고문헌 (13)
- "수돗물 배급수 계통의 유리잔류염소농도에 따른 종속영양세균의 거동에 관한 연구", 28(3), pp.9~18 (2002)
- "Efficiency comparison between chlorine and chlorine dioxide to control bacterial regrowth in water distribution system", 32(4), pp.282~291 (2006)
- "수질제어 및 부식억제제에 의한 상수도관의 내부부식 제어", 20(2), pp.215~223 (2006)
- "상수도 배급수시설 부식방지를 위한 부식억제제 적용의 현안과 과제", 8, pp.96~103 (2004)
- "배급수 계통에서 부식억제제 적용에 따른 부식과 적수와의 상관관계", 19(1), pp.68~77 (2005)
- "Passivation and its stability on copper in alkaline solutions containing carbonate and chloride ions. Corrosion Science", pp.287~296 (1990)
- "Phosphate inhibition of soluble copper corrosion by-product release", 44, pp.1057~1071 (2002)
- "On pitting corrosion of copper. Journal of American Water Works Association", pp.74~90 (1993)
- "상수도 배급수관망의 부식방지를 위한 인산염계 방청제 적용에 관한 연구", 29, pp.65~71 (2003)
- "Corrosion of copper pipes. Journal of American Water Works Association", pp.479~485 (1974)
- "Internal corrosion of water distribution system: Corrosion of copper in portable water system", pp.233~ (1996)
- "부식억제제를 이용한 Pilot Plant에서의 제철소 개방순환형 냉각시스템 부식제어에 관한 연구", 26(10), pp.1150~1157 (2004)
- "Copper dissolution in NaHCO3 and NaHCO3+NaCl aqueous solutions at pH 8. Journal of Electrochemical Society", pp.39~47 (1992)