수냉식변압기 냉각튜브의 부식특성 평가에 관한 연구

A Study on Evalution of Corrosion Properties in cooling tube of water cooling transformers

0

조회

0

다운로드

0

인용

0

참고문헌

키워드

주제분류금속공학

초록

Most of the thirteen substations in operation in the metropolitan area were installed around the year 2000, and since water cooling methods are used to directly withdraw heat from transformer oils, a stable supply of electric power is required through optimal maintenance of facilities. The water cooling tower installed outdoors, which uses the water supply as sprinkler water, experiences the most problems. Since more than 90% of the cooling water is reused, the dissolved composition in the water becomes concentrated due to long operating hours, and impurities dissolve in the water due to air flowing in from the outside, forming hard scales on the outer surface of the cooling tube, and in extreme cases, reacting with the tube material composition, leading to corrosion. As a result, not only is cooling efficiency lowered, but in extreme cases the cooling tube must be replaced. In this study, the characteristics and composition of the scales formed on the cooling tube were analyzed and corrosion characteristics of material types were identified in order to find an efficient maintenance method for cooling tubes. In addition, the degree of dissolution of various chemicals were investigated during the removal of scales that have been formed.

Abstract

Most of the thirteen substations in operation in the metropolitan area were installed around the year 2000, and since water cooling methods are used to directly withdraw heat from transformer oils, a stable supply of electric power is required through optimal maintenance of facilities. The water cooling tower installed outdoors, which uses the water supply as sprinkler water, experiences the most problems. Since more than 90% of the cooling water is reused, the dissolved composition in the water becomes concentrated due to long operating hours, and impurities dissolve in the water due to air flowing in from the outside, forming hard scales on the outer surface of the cooling tube, and in extreme cases, reacting with the tube material composition, leading to corrosion. As a result, not only is cooling efficiency lowered, but in extreme cases the cooling tube must be replaced. In this study, the characteristics and composition of the scales formed on the cooling tube were analyzed and corrosion characteristics of material types were identified in order to find an efficient maintenance method for cooling tubes. In addition, the degree of dissolution of various chemicals were investigated during the removal of scales that have been formed.

참고문헌 (11)

  1. 민성기, "수돗물의 pH가 동관의 부식에 미치는 영향", CORROSION SCIENCE AND TECHNOLOGY, 8(6), pp.233~238 (2009), 한국부식방식학회
  2. Y. H. Lee, "Principles and Prevention of Corrosion" (1999), DongHwa Technology publishing Co.
  3. J. S. Moon, "Optimization of Chemical Treatment Program in Cooling Tower Water System and Plume Dispersion Modeling", KEPRI, ~ (1997)
  4. J.W. McCoy, "The Chemical Treatment of Cooling Water, 2nd ed." (1983), Chemical Publishing Co.
  5. B.P. Boffardi, "Fundamentals of Cooling Water Treatment", 박사
  6. M. H. Harvey, "The Nalco Guide to Cooling Water System Failure Analysis" (1993), McGraw -Hill, Inc.
  7. "Handbook of X-ray Diffraction Spectrometry Rigaku Corp", ~ (1998)
  8. V. E. Buhrke, "A Practical Guide for the Preparation of Specimens for XRF and XRD Analysis" (1998), Wiley
  9. Rene E. Van Grieken, "Handbook of X-ray Spectrometry: 2nd Ed." (2002), Marcel Dekker Inc.
  10. R. Jenkins, "Practical X-ray Spectrometry" (1973), Springer-Verlag
  11. J. Goldstein, "Scanning Electron Microscopy and X-Ray Microanalysis" (2003), Springer

관련 논문AI추천

이 간행물의 다른 논문 (6건)