지역난방 냉각수 배관의 용접부 파손 분석
Failure Analysis of Welded type 304 in Cooling Water Pipeline of District Heating System
0
조회
0
다운로드
0
인용
0
참고문헌
키워드
초록
Failure analysis on the welded type 304 pipe used for cooling water piping in the district heating primary side was conducted. Inorganic elements and bacteria in the cooling water and in corrosion products were analyzed, and the weldment was inspected by microscopy and a sensitization test. Corrosion damages were observed in the heat-affected zone, on weld defects such as incomplete fusion or excessive penetration caused by improper welding, or/and at the 6 o'clock position along the pipe axial direction. However, the level of concentration of chloride in the cooling water as low as 80 ppm has been reported to be not enough for even a sensitized type 304 steel, meaning that the additional corrosive factor was required for these corrosion damages. The factor leading to these corrosion damages was drawn to be the metabolisms of the types of bacteria, which is proved by the detection of proton, sulfur containing species, biofilms, and both bacteria and corrosion product analyses.
Abstract
Failure analysis on the welded type 304 pipe used for cooling water piping in the district heating primary side was conducted. Inorganic elements and bacteria in the cooling water and in corrosion products were analyzed, and the weldment was inspected by microscopy and a sensitization test. Corrosion damages were observed in the heat-affected zone, on weld defects such as incomplete fusion or excessive penetration caused by improper welding, or/and at the 6 o'clock position along the pipe axial direction. However, the level of concentration of chloride in the cooling water as low as 80 ppm has been reported to be not enough for even a sensitized type 304 steel, meaning that the additional corrosive factor was required for these corrosion damages. The factor leading to these corrosion damages was drawn to be the metabolisms of the types of bacteria, which is proved by the detection of proton, sulfur containing species, biofilms, and both bacteria and corrosion product analyses.
참고문헌 (13)
- B. Skagestad, "District Heating and Cooling Connection Handbook", IEA District Heating and Cooling, ~ (1999)
- Minki Hong, "Failure Analysis of a Water Wall Boiler Tube for Power Generation in a District Heating System", Metals and Materials International, 25(5), pp.1191~1201 (2019), 대한금속·재료학회[DOI]
- 김영수, "지역난방 첨두부하보일러 대류부 부식 파손 분석", CORROSION SCIENCE AND TECHNOLOGY, 18(2), pp.55~60 (2019), 한국부식방식학회
- K. Eliseev, "District Heating System in Finland and Russia", Mikkeli University of Applied Sciences (2011)
- 홍민기, "지역난방 시스템의 순환수에 따른 보일러 튜브의 부식 특성", CORROSION SCIENCE AND TECHNOLOGY, 17(6), pp.287~291 (2018), 한국부식방식학회[DOI]
- N. R. Taylor, "District Heating Handbook", International District Heating Association, ~ (1983)
- 이철구, "AISI 316L 클래드강의 맞대기 용접부 입계부식과 예민화 거동에 관한 연구", 대한용접접합학회지, 31(2), pp.49~56 (2013), 대한용접접합학회
- 오은종, "304 스테인리스강 용접 열영향부의 입계 부식에 미치는 탄소함량의 영향", 대한용접접합학회지, 37(4), pp.322~332 (2019), 대한용접접합학회[DOI]
- Duncan Munro, "Operational Guidelines and Code of Practice (OGCP) for Stainless Steel Products in Drinking Water Supply, in OGCP for Stainless Steel Products - DWI Application 56.4.477", The Steel Construction Institute (SCI), ~ (2002)
- C. P. Dilton, "Corrosion resistance of stainless steels", pp.96~ (1995), Marcel Dekker, Inc
- D. H. Pope, "Fundamentals of MIC in Water-Based Fire Protection Sprinkler Systems", Fire Protection Contractor magazine, ~ (2014)
- D. A. Jones, "Principles and Prevention of Corrosion", pp.377~ (1996), Prentice-Hall, Inc
- M. G. Fontana, "Corrosion Engineering", pp.394~ (1986), McGraw-Hill, Inc