본문 바로가기
KERD
논문

보건의료시설의 실내 예상 평균 온열감(PMV), 이산화탄소 농도, 소음도, 조도의 통합실내쾌적도(IEQh)를 통한 연간 실내 쾌적도 평가

Evaluation of Annual Indoor Environment Quality in Hospitals using Various Comfort-related Factors

0

조회

0

다운로드

2

인용

0

참고문헌

키워드

초록

Objectives: A hospital is a complex building that serves many different purposes. The indoor environment in a hospital plays a major role in patient well-being and the work efficiency of the hospital staff. This study was conducted to evaluate overall comfort in two major hospitals over the course of one year. Methods: Various indoor environmental conditions were measured in two general hospitals for one year (April 2014 to April 2015). Monitoring alternated between the hospitals at one month per respective monitoring session. The indoor air temperature, relative humidity (RH), mean radiant temperature and air velocity were measured in order to calculate the predicted mean vote (PMV). Carbon dioxide concentration, noise level and illumination level were concurrently measured and applied to the overall IEQ acceptance model for the hospitals (IEQh). Results: The IEQh at the two general hospitals was different at five spaces within a building. The IEQh for summer and winter were significantly different. Real-time IEQh demonstrated that indoor comfort was affected by the hospital's operating hours due to operation of the HVAC system. The percentage of indoor comfort in the hospitals was higher using PMV than IEQh. Conclusion: IEQh in the hospitals was different at locations with different purposes. Indoor comfort assessment using IEQh was stricter than with PMV. Additional research is needed in order to optimize the IEQh model.

Abstract

Objectives: A hospital is a complex building that serves many different purposes. The indoor environment in a hospital plays a major role in patient well-being and the work efficiency of the hospital staff. This study was conducted to evaluate overall comfort in two major hospitals over the course of one year. Methods: Various indoor environmental conditions were measured in two general hospitals for one year (April 2014 to April 2015). Monitoring alternated between the hospitals at one month per respective monitoring session. The indoor air temperature, relative humidity (RH), mean radiant temperature and air velocity were measured in order to calculate the predicted mean vote (PMV). Carbon dioxide concentration, noise level and illumination level were concurrently measured and applied to the overall IEQ acceptance model for the hospitals (IEQh). Results: The IEQh at the two general hospitals was different at five spaces within a building. The IEQh for summer and winter were significantly different. Real-time IEQh demonstrated that indoor comfort was affected by the hospital's operating hours due to operation of the HVAC system. The percentage of indoor comfort in the hospitals was higher using PMV than IEQh. Conclusion: IEQh in the hospitals was different at locations with different purposes. Indoor comfort assessment using IEQh was stricter than with PMV. Additional research is needed in order to optimize the IEQh model.

참고문헌 (13)

  1. Fanger PO, "Assessment of man's thermal comfort in practice", British journal of industrial medicine, 30(4), pp.313~324 (1973)
  2. Wong LT, "A multivariate-logistic model for acceptance of indoor environmental quality(IEQ)in offices", Building and Environment, 43(1), pp.1~6 (2008)
  3. Cao B, "Development of a multivariate regression model for overall satisfaction in public buildings based on field studies in Beijing and Shanghai", Building and Environment, 47, pp.394~399 (2012)
  4. Lee B, "Evaluation of overall comfort in hospitals in summer using various comforts related factors", pp.2015
  5. Balaras CA, "HVAC and indoor thermal conditions in hospital operating rooms", Energy and Buildings, 39(4), pp.454~470 (2007)
  6. Pourshaghaghy A, "Examination of thermal comfort in a hospital using PMV–PPD model", Applied ergonomics, 43(6), pp.1089~1095 (2012)
  7. Khodakarami J, "Achieving thermal comfort in Iranian hospitals" (2008), University of Wales
  8. Hwang RL, "Patient thermal comfort requirement for hospital environments in Taiwan", Building and environment, 42(8), pp.2980~2987 (2007)
  9. Wang F, "Field evaluation of thermal comfort and indoor environment quality for a hospital in a hot and humid climate", HVAC&R Research, 18(4), pp.671~680 (2012)
  10. 박유원, "한국형 아파트의 난방에너지 분석 3:실내설정조건의 영향", 설비공학 논문집, 17(8), pp.722~728 (2005), 대한설비공학회
  11. Nikolopoulou M, "Thermal comfort and psychological adaptation as a guide for designing urban spaces", Energy and Buildings, 35(1), pp.95~101 (2003)
  12. Lai JH, "Perception of importance and performance of the indoor environmental quality of high-rise residential buildings", Building and Environment, 44(2), pp.352~360 (2009)
  13. Choi JH, "Decision support for improving occupant environmental satisfaction in office buildings: The relationship between sub-set of IEQ satisfaction and overall environmental satisfaction", Proceedings of the 9th International Conference Healthy Buildings (2009)

관련 논문AI추천