In this study, to develop and verify the Jeju-type groundwater thermal system design program, the energy consumption and system performance derived by input into the design program based on the load calculated on the demonstration site and the groundwater temperature were compared and analyzed with the actual measured values. The theoretical values ​​of energy consumption and heating and cooling COP ​​obtained through the Jeju-type groundwater thermal system design program were 11.24kW, 5.28 for heating, 13.31kW, 3.94 for cooling respectively. The measured values ​​of energy consumption and COP of the Jeju-type groundwater thermal system were 3967.2kW and 4.5, respectively. The error between the theoretical value and the measured value obtained through the design program is 0% and 2.39%, respectively. The errors that occur in the predicted values ​​and the actual values ​​are due to variables that are ignored in the system assumptions. If users consider errors and use it when designing groundwater thermal systems, they can estimate the cost of required drilling works, heat exchangers, and heat pumps and analyze economic feasibility.

Abstract

In this study, to develop and verify the Jeju-type groundwater thermal system design program, the energy consumption and system performance derived by input into the design program based on the load calculated on the demonstration site and the groundwater temperature were compared and analyzed with the actual measured values. The theoretical values ​​of energy consumption and heating and cooling COP ​​obtained through the Jeju-type groundwater thermal system design program were 11.24kW, 5.28 for heating, 13.31kW, 3.94 for cooling respectively. The measured values ​​of energy consumption and COP of the Jeju-type groundwater thermal system were 3967.2kW and 4.5, respectively. The error between the theoretical value and the measured value obtained through the design program is 0% and 2.39%, respectively. The errors that occur in the predicted values ​​and the actual values ​​are due to variables that are ignored in the system assumptions. If users consider errors and use it when designing groundwater thermal systems, they can estimate the cost of required drilling works, heat exchangers, and heat pumps and analyze economic feasibility.

참고문헌 (9)

  1. Y. D. Kim, "Technology, Marketplace and Industrial Trend of Heat Pump", Journal of the Korean Society of Mechanical Technology, 12(3) (2010)
  2. 권영철, "냉각제습 및 혼합과정에 의한 백연저감 열교환 시스템의 열전달 성능", 한국기계기술학회지, 23(6), pp.1112~1118 (2021), 한국기계기술학회[DOI]
  3. 공민석, "수평형 지중열교환기의 열전달 및 압력강하 특성에 관한 수치해석적 연구", 한국기계기술학회지, 21(5), pp.916~922 (2019), 한국기계기술학회[DOI]
  4. Kasuda. T, "Earth Temperature and Thermal Diffusivity at Selected Stations in the United States", ASHRAE Transactions, 71(Part 1) (1965)
  5. 문종필, "공기열 히트펌프와 경유온풍기의 하이브리드식 최적운용기술연구", 한국기계기술학회지, 17(5), pp.1098~1106 (2015), 한국기계기술학회[DOI]
  6. 김용환, "비활성 화산지역의 지중공기열원 에너지 이용에 관한 실험적 연구", 한국태양에너지학회 논문집, 34(5), pp.73~80 (2014), 한국태양에너지학회
  7. H. Brandl, "Energy foundations and other Thermo-Active ground structures", Geo-technique, 56(2), pp.81~122 (2006)
  8. 강경문, "지하수 열원 지중 열교환기의 열적 특성에 관한 실험적 연구", 한국기계기술학회지, 21(4), pp.593~599 (2019), 한국기계기술학회[DOI]
  9. 김민준, "제주도에 설치된 지열 열펌프 시스템용 제주형 지중열교환기의 열특성 연구", 한국산학기술학회논문지, 21(2), pp.32~38 (2020), 한국산학기술학회[DOI]