케이블 장력 및 피뢰기의 강성 변화를 고려한 애자형 피뢰기의 동특성 시험 연구
Experimental Study on the Dynamic Characteristics of Porcelain Surge Arrestor Considering the Variation of Cable’s Tension and Arrestor’s Stiffness
1
조회
0
다운로드
1
인용
0
참고문헌
키워드
초록
Porcelain surge arrestor is very vulnerable to earthquake but there is very few information on its dynamic characteristics which are necessary to the seismic design. Therefore, the dynamic characteristics of the porcelain surge arrestor are evaluated considering the variation of its cable tension and stiffness by shaking table test. The test results show that the first natural frequencies are 5.3 Hz and 5.2 Hz in the horizontal x- and y-axis directions, respectively, and higher than 30 Hz in the vertical z-axis direction, respectively. The installation of cable on the surge arrestor reduces the horizontal natural frequencies due to the constraint effect of the cable but cable tension has no effect on the natural frequency. Also, the natural frequency is proportional to the stiffness of the surge arrestor. This test result will be used for the seismic design and seismic capacity assessment of domestic substations and contribute to the stability of the electric power supply under earthquake event.
Abstract
Porcelain surge arrestor is very vulnerable to earthquake but there is very few information on its dynamic characteristics which are necessary to the seismic design. Therefore, the dynamic characteristics of the porcelain surge arrestor are evaluated considering the variation of its cable tension and stiffness by shaking table test. The test results show that the first natural frequencies are 5.3 Hz and 5.2 Hz in the horizontal x- and y-axis directions, respectively, and higher than 30 Hz in the vertical z-axis direction, respectively. The installation of cable on the surge arrestor reduces the horizontal natural frequencies due to the constraint effect of the cable but cable tension has no effect on the natural frequency. Also, the natural frequency is proportional to the stiffness of the surge arrestor. This test result will be used for the seismic design and seismic capacity assessment of domestic substations and contribute to the stability of the electric power supply under earthquake event.
참고문헌 (9)
- KEPCO Research Institute, "Seismic design guidelines for transmission and substation facilities", ~ (2001)
- EERI, "Northridge reconnaissance report, Earthquake Spectra, Supplement C", ~ (1995)
- The Hanshin-Awaji earthquake of January 17, 1995 : Performance of lifelines, "Shinozuka M", ~, pp.Technical Report NCEER-95-0015 (1995)
- 장정범, "변압기의 내진성능 향상을 위한 마찰진자 면진장치의 시험 연구", 한국지진공학회논문집, 12(2), pp.1~8 (2008), 한국지진공학회
- 장정범, "무정전-무이설 방식의 전기판넬 내진보강시스템 시험연구", 한국지진공학회논문집, 13(3), pp.1~10 (2009), 한국지진공학회
- Seismic Evaluation of 550kV Porcelain Transformer Bushings, "Gilani AS", PEER, ~ (1999)
- Seismic Evaluation of 196kV Porcelain Transformer Bushings, "Gilani AS", PEER, ~ (1999)
- Demonstration of CERL Equipment Fragility and Protection Procedure by Fragility Testing of a Power Transformer Bushing, "Wilcoski J", ~, pp.ATC-29-1 (1997)
- Ground Motion Amplification at Base of Bushings Mounted on Electric Substation Transformer, "Villaverde R", Department of Civil Engineering, University of California, ~, pp.PEER (1999), PG&E Under Award No. PGE-09566