154 kV 및 345 kV 주변압기 부싱의 내진성능 시험 연구
The Experimental Study on Seismic Capacity of 154 kV & 345 kV Main Transformer Bushings
1
조회
0
다운로드
1
인용
0
참고문헌
키워드
초록
In this study, seismic performance of bushings and their connection parts was analyzed by performing shaking table tests for various types of bushings widely used as auxiliary equipment of main transformers in domestic substations. As a result of the seismic tests of five types of 154 kV bushings according to the manufacturers, all the bushings secured the structural integrity even at the acceleration of 1.4 g and it was found that leakage of insulating oil didn't occur. Also, the average acceleration amplification rate at the upper part of the bushings was about 2.5 to 3.0 times higher than the lower one. On the other hand, when a representative 345 kV bushing was subjected to the seismic test, the structural integrity was secured even at 1.0 g acceleration similar to the design earthquake load level, but in this test, leakage of insulating oil occurred. However, when a stiffener restricting the connection of the bushing is installed in the same 345 kV bushing, the displacement of the bushing connection is controlled and the stiffener prevent the oil from leaking even at the acceleration of the designed seismic level.
Abstract
In this study, seismic performance of bushings and their connection parts was analyzed by performing shaking table tests for various types of bushings widely used as auxiliary equipment of main transformers in domestic substations. As a result of the seismic tests of five types of 154 kV bushings according to the manufacturers, all the bushings secured the structural integrity even at the acceleration of 1.4 g and it was found that leakage of insulating oil didn't occur. Also, the average acceleration amplification rate at the upper part of the bushings was about 2.5 to 3.0 times higher than the lower one. On the other hand, when a representative 345 kV bushing was subjected to the seismic test, the structural integrity was secured even at 1.0 g acceleration similar to the design earthquake load level, but in this test, leakage of insulating oil occurred. However, when a stiffener restricting the connection of the bushing is installed in the same 345 kV bushing, the displacement of the bushing connection is controlled and the stiffener prevent the oil from leaking even at the acceleration of the designed seismic level.
참고문헌 (8)
- Minstry of the Interior, "Common applications of seismic design criteria", ~ (2017)
- 장정범, "변압기의 내진성능 향상을 위한 마찰진자 면진장치의 시험 연구", 한국지진공학회논문집, 12(2), pp.1~8 (2008), 한국지진공학회
- 장정범, "무정전-무이설 방식의 전기판넬 내진보강시스템 시험연구", 한국지진공학회논문집, 13(3), pp.1~10 (2009), 한국지진공학회
- 장정범, "케이블 장력 및 피뢰기의 강성 변화를 고려한 애자형 피뢰기의 동특성 시험 연구", 한국지진공학회논문집, 18(5), pp.253~259 (2014), 한국지진공학회
- 日本電氣協會, "変電所等における電氣設備の耐震設計指針, JEAG 5003", ~ (2010)
- Institute of Electrical and Electronics Engineers, "IEEE Recommended Practice for Seismic Design of Substations, IEEE Std 693", ~ (2005)
- 조양희, "진동시험에 의한 154kV 변압기 부싱의 동특성 분석 및 내진성능 평가", 한국지진공학회논문집, 10(5), pp.107~115 (2006), 한국지진공학회
- Korea Electric Power Cooperation, "Seismic design guidelines for transmission, substation and distribution facilities", ~ (2014)