플랜트 설비 지지용 대안 강구조 시스템의 내진성능
Seismic Performance of Alternative Steel Structural Systems for an Equipment-Supporting Plant Structure
1
조회
0
다운로드
0
인용
0
참고문헌
키워드
초록
In this study, alternative seismic force-resisting systems for plant structure supporting equipment were designed, and the seismic performance thereof was compared using nonlinear dynamic analysis. One alternative seismic force-resisting system was designed per the requirement for ordinary moment-resisting and concentrically braced frames but with a reduced base shear. The other seismic force-resisting system was designed by accommodating seismic details of intermediate and unique moment-resisting frames and special concentrically braced frames. Different plastic hinge models were applied to ordinary and ductile systems based on the validation using existing test results. The control model obtained by code-based flexible design and/or reduction of base shear did not satisfy the seismic performance objectives, but the alternative structural system did by strengthened panel zones and a reduced effective buckling length. The seismic force to equipment calculated from the nonlinear dynamic analysis was significantly lower than the equivalent static force of KDS 41 17 00. The comparison of design alternatives showed that the seismic performance required for a plant structure could be secured economically by using performance-based design and alternative seismic-force resisting systems adopting minimally modified seismic details.
Abstract
In this study, alternative seismic force-resisting systems for plant structure supporting equipment were designed, and the seismic performance thereof was compared using nonlinear dynamic analysis. One alternative seismic force-resisting system was designed per the requirement for ordinary moment-resisting and concentrically braced frames but with a reduced base shear. The other seismic force-resisting system was designed by accommodating seismic details of intermediate and unique moment-resisting frames and special concentrically braced frames. Different plastic hinge models were applied to ordinary and ductile systems based on the validation using existing test results. The control model obtained by code-based flexible design and/or reduction of base shear did not satisfy the seismic performance objectives, but the alternative structural system did by strengthened panel zones and a reduced effective buckling length. The seismic force to equipment calculated from the nonlinear dynamic analysis was significantly lower than the equivalent static force of KDS 41 17 00. The comparison of design alternatives showed that the seismic performance required for a plant structure could be secured economically by using performance-based design and alternative seismic-force resisting systems adopting minimally modified seismic details.
참고문헌 (14)
- "KDS 41 17 00. Seismic Building Design Code", Korea Construction Standards Center, ~ (2019)
- Kwak BH, "Comparison of Seismic Performance and Material Quantity between Code-based and Performancebased Seismic Design of a Equipment-Supporting Plant Structure", EESK Workshop, pp.21~22 (2022)
- Oh SH, "Experimental verification of seismic performance of built-up beam-to-column connections with ductile detail", Journal of Consturctional Steel Research (2021)
- 김선희, "건축구조용강재(SN490) 조립 H형강 기둥-보 접합부의 이력거동에 관한 실험적 연구", 한국강구조학회 논문집, 20(6), pp.807~815 (2008), 한국강구조학회
- 오상훈, "SN 강재가 사용된 강구조 용접모멘트접합부의 내진성능 평가", 한국강구조학회 논문집, 22(3), pp.271~280 (2010), 한국강구조학회
- "KDS 41 31 00. Korean Building Code for Steel Structures", Korea Construction Standards Center, ~ (2019)
- Kim SY, "Seismic Performance Evaluation of Beam-Column Connection for Panel Zone Strength", Journal of Korean Society of Hazard Mitigation, 7(1), pp.11~20 (2007)
- 이철호, "RBS 철골모멘트접합부의 내진성능에 대한 패널존 강도의 영향", 한국지진공학회논문집, 10(3), pp.149~158 (2006), 한국지진공학회
- A. Moslehi Tabar, "Instability of beams with reduced beam section moment connections emphasizing the effect of column panel zone ductility", Journal of Constructional Steel Research, 61(11), pp.1475~1491 (2005)
- American Society of Civil Engineers, "ASCE 41-17 Seismic Evalution and Retrofitting Techniques for Unreinforced Masonry Buildings", ~ (2017)
- National Institute of Standards and Technology, "Recommended modeling parameters and acceptance criteria for nonlinear analysis in support of seismic evaluation, retrofit, and design. NIST GCR 17-917-45", ~ (2017)
- 한상환, "WUF-B 접합부의 내진성능 평가 (1) WUF-B 접합부의 반복가력 실험", 대한건축학회논문집 구조계, 19(11), pp.33~40 (2003), 대한건축학회
- 이철호, "용접 수평헌치로 보강된 철골 모멘트 접합부의반복재하 내진실험", 한국지진공학회논문집, 6(4), pp.31~37 (2002), 한국지진공학회
- Evaluation of the FEMA P-695 Methodology for Quantification of Building Seismic Performance Factors, "National Institute of Standards and Technology", ~ (2010)