3상 양방향 인버터의 계통전압 불평형 및 왜곡에 의한 계통전류 보상
The Compensation of the Grid Current Distortion caused by the Grid Voltage Unbalance and Distortion for 3-Phase Bi-Directional DC to AC Inverter
0
조회
0
다운로드
2
인용
0
참고문헌
키워드
초록
This paper presents the algorithm of the compensation of the grid current distortion caused by the grid voltage unbalance and distortion in 3-phase bi-directional DC to AC inverter. Usually 3-phase grid system has unbalance and distortion because of connecting 1-phase and non-linear load with 3-phase load using same input node. Controlling 3-phase inverter by general method under the unbalanced and distorted grid voltage, the grid current has distortion. This distortion of the grid current cause the grid voltage distortion again. So, it need to control the grid current balanced and non-distorted, even the grid voltage gets unbalanced and distorted. There are some complex method to compensate the gird current distortion. it sugest simple method to solve the problem. PSIM simulation is used to validate the proposed algorithm.
Abstract
This paper presents the algorithm of the compensation of the grid current distortion caused by the grid voltage unbalance and distortion in 3-phase bi-directional DC to AC inverter. Usually 3-phase grid system has unbalance and distortion because of connecting 1-phase and non-linear load with 3-phase load using same input node. Controlling 3-phase inverter by general method under the unbalanced and distorted grid voltage, the grid current has distortion. This distortion of the grid current cause the grid voltage distortion again. So, it need to control the grid current balanced and non-distorted, even the grid voltage gets unbalanced and distorted. There are some complex method to compensate the gird current distortion. it sugest simple method to solve the problem. PSIM simulation is used to validate the proposed algorithm.
참고문헌 (8)
- V. Blasko, "A new mathematical model and control of a three-phase AC-DC voltage source converter", IEEE Transactions on Power Electronics, 12(1), pp.116~123 (1997)
- P. Enjeti, "A new control strategy to improve the performance of a PWM AC to DC converter under unbalanced operating condi tions", pp.382~389 (1991), Proc. IEEE PESC Conf
- H. S. Song, "Dual current controller PWM converter under unbalanced input voltage conditions", IEEE Trans. on Ind. Elec, 46(5), pp.953~959 (1999)
- M. Liserre, "Multiple harmonics control for three-phase grid converter systems with the use of PI-RES current controller in a rotating frame", IEEE Trans. on Power Elec, 21(3), pp.836~841 (2006)
- M. T. Tsai, "Analysis and Design of Three Phase AC to DC Converters With High Power Factor and Near-Optimum Feedforward", IEEE Transactions on Industrial Electronics, 46(3) (1999)
- J. I. Jang, "Current Control of Three-Phase PWM Converters under Unbalanced and Distorted Source Voltage", KIPE Transactions, 12(1), pp.27~36 (2007)
- S. D. Yang, "The Study of 3-Phase Bi-Directional DC to AC Inverter for the Bi-Modal PV PCS", The Korean Solar Energy Society Spring Annual Conference, 32(1), pp.319~324 (2012)
- 김지원, "A Study on Sensorless Control of Transverse Flux Rotating Motor Based on MRAS with Parameter Estimation", 전력전자학회 영문논문지, 11(6), pp.864~869 (2011), 전력전자학회