환기장치가 설치된 중학교 교실에서 탄산가스 농도변화 측정 및 모델링
CO2 Gas Concentration Measurement and Modeling at a Classroom with Ventilation System of Middle School in Pusan
0
조회
0
다운로드
2
인용
0
참고문헌
초록
Abstract
This study describes to analyze variation of carbon dioxide gas concentration by experimental and theoretical method according to the using patterns of ventilation system in a model classroom. Concentration of CO2 gas varied by the occupancy and the ventilation systems are operating or not. More than 850 CMH ventilation system can maintain CO2 gas concentration lower than 1,000 ppm along the class time and can be adopted the government guideline. Theoretical modeling of the concentration was performed at well-mixed ideal condition. Delays of concentration decay were shown at each case compared to actual.Keywards : 환기(Ventilation), 농도(Concentration), 교실(Classroom), 탄산가스(Carbon dioxide)기 호 설 명