Newly designed vapor-injection heat pumps have been proposed and analyzed in the present study. An economizer- type vapor-injection (V-I) system has been employed as the standard system because of its reliability and simple control method. The V-I system has a re-cooler and re-heater for cooling and heating, respectively. Solar panels have been installed in the V-I heat pump as well as in the re-heater in order to enhance heating capacity and performance. R410A has been employed as a working fluid and performance analysis has been conducted under various conditions. Results are summarized as follows: (1) The V-I system with the re-cooler yielded a marginally higher coefficient of performance (COP) than the conventional V-I refrigeration system. (2) By increasing the re-cooler cooling capacity, enhanced system performance as compared to the conventional V-I system was observed. (3) The re-heater negatively affected the system performance; hence, the V-I heat pump with the re-heater yielded a lower COP than that of the conventional V-I heat pump used for heating. (4) Although the solar panels increased the system performance, this increase could not offset performance degradation by the re-heater.

Abstract

Newly designed vapor-injection heat pumps have been proposed and analyzed in the present study. An economizer- type vapor-injection (V-I) system has been employed as the standard system because of its reliability and simple control method. The V-I system has a re-cooler and re-heater for cooling and heating, respectively. Solar panels have been installed in the V-I heat pump as well as in the re-heater in order to enhance heating capacity and performance. R410A has been employed as a working fluid and performance analysis has been conducted under various conditions. Results are summarized as follows: (1) The V-I system with the re-cooler yielded a marginally higher coefficient of performance (COP) than the conventional V-I refrigeration system. (2) By increasing the re-cooler cooling capacity, enhanced system performance as compared to the conventional V-I system was observed. (3) The re-heater negatively affected the system performance; hence, the V-I heat pump with the re-heater yielded a lower COP than that of the conventional V-I heat pump used for heating. (4) Although the solar panels increased the system performance, this increase could not offset performance degradation by the re-heater.

참고문헌 (6)

  1. M. Guoyuan, "Experimental investigation of air-source heat pump for cold regions", International Journal of Refrigeration, 26(1), pp.12~18 (2003)
  2. M. G. Yuan, "Experimental study of a heat pump system with flash-tank coupled with scroll compressor", Energy and Buildings, 40(5), pp.697~701 (2008)
  3. X. Xu, "Refrigeant injection for heat pumping", air conditioning systems: Literature review and chanllenges discussions, 2011, pp.34(2), 402~415
  4. M. M. Mathison, "Performance limit for economized cycles with continuous refrigerant injection", International Journal of Refrigeration, 34(1), pp.234~242 (2011)
  5. "AspenTech"[URL]
  6. D. Y. Peng, "A new Two-Constant Equation of State", Industrial & Engineering Chemistry Fundamentals, 15(1), pp.59~64 (1976)