모세관 삽입 룸 에어컨용 액·가스 열교환 배관에 관한 실험적 연구
An Experimental Study of Liquid?Gas Heat Exchange Pipe InsertedCapillary Tube for Room Air-Conditioner
0
조회
0
다운로드
0
인용
0
참고문헌
키워드
초록
Abstract
This study shows the experimental characteristics of the double pipe inserted liquid pipe with small diameter in the gas pipe with large diameter for circulating of a liquid of high temperature, pressure and a gas of low temperature, pressure at the same time. So the functions of pipe and pipe's expansion and heat transfer are presented simultaneously. In the result, the temperature of gas refrigerant at the inlet of compressor increased about 5℃ by the heat transfer with liquid refrigerant in case of the double pipe. And liquidgas refrigerant which the temperature at the inlet of evaporator decreased about 3℃ comparing with the existing type flows into an evaporator. COP of the double pipe increased about 7~10% comparing with that of the conventional pipe. And the noise of the double pipe at capillary tube is less than that of the conventional type about 3dB. Consequently, it is convinced the superiority of the double pipe in the heat loss and soundproofing aspect.