Corrosion Performance of Cu Bonded Grounding-Electrode by Accelerated Corrosion Test
0
조회
0
다운로드
0
인용
0
참고문헌
키워드
초록
Natural degradation of grounding-electrode in soil environment should be monitored for several decadesto predict the lifetime of the grounding electrode for efficient application and management. However,long-term studies for such electrodes have many practical limitations. The conventional acceleratedcorrosion test is unsuitable for such studies because simulated soil corrosion process cannot representthe actual soil environment. A preliminary experiment of accelerated corrosion test was conductedusing existing test standards. The accelerated corrosion test that reflects the actual soil environmenthas been developed to evaluate corrosion performances of grounding-electrodes in a short period. Severaltest conditions with different chamber temperatures and salt spray were used to imitate actual fieldconditions based on ASTM B162, ASTM B117, and ISO 14993 standards. Accelerated degradationspecimens of copper-bonded electrodes were made by the facile method and their corrosion performanceswere investigated. Their corrosion rates were calculated to 0.042 μm/day, 0.316 μm/day, and 0.11μm/day, respectively. These results indicate that accelerated deterioration of grounding materials canbe determined in a short period by using cyclic test condition with salt spray temperature of 50 °C.
Abstract
Natural degradation of grounding-electrode in soil environment should be monitored for several decadesto predict the lifetime of the grounding electrode for efficient application and management. However,long-term studies for such electrodes have many practical limitations. The conventional acceleratedcorrosion test is unsuitable for such studies because simulated soil corrosion process cannot representthe actual soil environment. A preliminary experiment of accelerated corrosion test was conductedusing existing test standards. The accelerated corrosion test that reflects the actual soil environmenthas been developed to evaluate corrosion performances of grounding-electrodes in a short period. Severaltest conditions with different chamber temperatures and salt spray were used to imitate actual fieldconditions based on ASTM B162, ASTM B117, and ISO 14993 standards. Accelerated degradationspecimens of copper-bonded electrodes were made by the facile method and their corrosion performanceswere investigated. Their corrosion rates were calculated to 0.042 μm/day, 0.316 μm/day, and 0.11μm/day, respectively. These results indicate that accelerated deterioration of grounding materials canbe determined in a short period by using cyclic test condition with salt spray temperature of 50 °C.
참고문헌 (10)
- M. Romanoff, "Underground Corrosion, National Bureau of Standards, Circular 579", ~ (1957)
- Richard W. Drisko, "Field Testing of Electrical Grounding Rods", Naval Civil Engineering Laboratory, ~ (1970)
- A Technical Report on the Service Life of Ground Rod Electrodes, "Chris Rempe", ERICO, ~ (2003)
- National Electrical Grounding Research Project, "Travis Lindsey", The Fire Protection Research Foundation, ~ (2007)
- Marek Loboda, , Proc. 28th International Conf. on Lightning Protection, International Conference on Lightning, pp.644~ (2006)
- F. D. Alessandro, , IAEI NEWS, 79~ (2008)
- "EN50164-2, Lightning Protection Components (LPC) Part 2: Requirements for Conductors and Earth Electrodes, Annex B", ~ (2002)
- "ASTM B162-99, Standard Practice for Conducting and Evaluating Laboratory Corrosion Tests in Soils", ~ (2010)
- "ASTM B117-11, Standard Practice for Operating Salt Spray (Fog) Apparatus", ~ (2011)
- "ISO14993, Corrosion of Metals and Alloys - Accelerated Testing Involving Cyclic Exposure to Salt Mist, "Dry" and "Wet" Conditions", ~ (2011)