In this study, we investigated the possibility of auto control and the proper operating factors in the BNR(Biological Nutrient Removal) process using an NADH(Reduced Nicotinamide Adenine Dinucleotide) fluorometer, which characterized the emitted fluorescence when activated by flashes of UV light at 460 nm. In terms of finding adequate operating parameters, results indicted that nitrification efficiency decreased in the controlled DO while denitrification efficiency decreased in the controlled pH. The above results indicated that controlled operating condition after combination with NADH, DO and pH was resonable. Result obtained from the correlation between NADH and pH showed that variation trend of influent loading was similar to those of NADH and pH, and also the variation cycle was repeated on a daily basis. Consequently, this result showed the increase of BOD loading caused the nitrification efficiency to decrease because air-flow, required for nitrification, was reduced, and so the NADH value was increased. From these results, it is possible to use NADH flourimetry to assess the variation of organic load and nitrification efficiency in the case of small change in influent pH such as in sewage and also to handle and operate the load variation in the auto control system using the NADH fluorometer.
Abstract
In this study, we investigated the possibility of auto control and the proper operating factors in the BNR(Biological Nutrient Removal) process using an NADH(Reduced Nicotinamide Adenine Dinucleotide) fluorometer, which characterized the emitted fluorescence when activated by flashes of UV light at 460 nm. In terms of finding adequate operating parameters, results indicted that nitrification efficiency decreased in the controlled DO while denitrification efficiency decreased in the controlled pH. The above results indicated that controlled operating condition after combination with NADH, DO and pH was resonable. Result obtained from the correlation between NADH and pH showed that variation trend of influent loading was similar to those of NADH and pH, and also the variation cycle was repeated on a daily basis. Consequently, this result showed the increase of BOD loading caused the nitrification efficiency to decrease because air-flow, required for nitrification, was reduced, and so the NADH value was increased. From these results, it is possible to use NADH flourimetry to assess the variation of organic load and nitrification efficiency in the case of small change in influent pH such as in sewage and also to handle and operate the load variation in the auto control system using the NADH fluorometer.
참고문헌 (21)
- Vaboliene, G., "Investigation into biologocal nutrient removal from wastewater", Journal of Environmental Engineering and Landscape Management, 8(4), pp.177~181 (2005)
- Harrison, D. E. F., "Fluorometric technique for monitoring changes in the level of reduced nicotinamide nucleotides in continuous culture of microorganisms", Applied and Environmental Microbiology, 19, pp.446~449 (1970)
- Armiger, W. B., "Automated on-line control strategy for the optimization of nutrient removal processes", Fifth IAWQ Workshop on Instrumentation, Control and Automation of Water and Wastewater Treatment and Transport System, Japan, 26 July (1990)
- Teusink, B, "Exposinga complex metabolic system : glycolysis in saccharomyces cerevisiae", 박사, pp.1990
- Yang, X., "Apparatus and method for monitoring and controlling biological activity in wastewater and controlling the treatment thereof, US Patent 5552319", ~ (1996)
- Mah, T. J., "Use of culture fluorescence monitoring for control and optimization of biological nutrient removal form wastewaters", 박사, pp.1995
- Chance, B., "The respiratory chain and oxidative phosphory-lation", Advanced Enzymnology, 17, pp.65~134 (1956)
- Trivedi, H., "Simultaneous nitrification", denitrification by monitoring NADH fluorescence in activated sludge, 2000, 2262~2278
- Industrial Waste- water, "Trivedi, H.", Water Environment Federation, 5~7 (2002)
- Rittman, B. E., "Simultaneous denitrification with nitrification in single-channel oxidation ditches", Journal of Water Pollution Control Federation, 57, pp.300~308 (1985)
- Van Huyssteen, J. A., "The olifantsfontein nutrient removal plant", Water Science and Technology, 22, pp.1~8 (1990)
- Srivastava, S., "Use of NADH fluorescence measurement for on-line biomass estimation and characterization of metabolic status in bioreactor cultivation of plant cells for azadirachtin (a biopesticide) production", Process Biochemistry (2008)
- Huang, L., "Sludge settling and online NAD(P)H fluorescence profiles in wastewater treatment bioreactors operated at low dissolved oxygen concentrations", Water Research, 41, pp.1877~1884 (2007)
- Helmo, K., "Novel method for the control of biodegradation, EP No. 0 828 692 B1", ~ (1996)
- Ju, L. K., "Monitoring and kinetic study of ammonia oxidation using dissolved oxygen electrode and NAD(P)H fluorometer", Water Research, 37, pp.188~196 (2003)
- 김영규, "미생물 코팅 담체를 이용한 하수의 질소?인 제거에 관한 연구", 한국환경보건학회지, 32(1), pp.27~35 (2006), 한국환경보건학회
- Lee, W. I., "The Analysis of NADH Fluorescence Signal in the Biological Nitrogen", 상하수도학회지, pp.223~228 (2005)
- Melissa Wos and Peter Pollard, "Sensitive and meaningful measures of bacterial metabolic activity using NADH fluorescence", Water Research, 40, pp.2084~2092 (2006)
- Lee, W. I., "Characteristic of NADH Fluorescence Sensor for Online Aeration Control of Biological Nitrogen Removal Process", 2006 Academic Conference, Korean Society on Water Quality, pp.67~72 (2006), Korean Society of Water and Wastewater
- Oh, K. K, "A Study on the Simultaneous Nitrification and Denitrification with NADH Sensor in Oxdiation Ditch Process", 석사, pp.2006
- Chen, F., "Aerobic denitrification of pseudomonas aeruginosa monitored by online NAD(P)H fluorescence", Applied and Environmental Microbiology, 69(11), pp.6715~6722 (2003)