본문 바로가기
KERD
논문

60Hz 고압송전선로 인접 주거지역의 자기장 노출수준 평가

Evaluation of the Magnetic Field Exposure Level in 60Hz High Voltage Transmission Lines Nearby Residential Area

1

조회

0

다운로드

10

인용

0

참고문헌

키워드

초록

In order to evaluate the magnetic field(MF) exposure level in residential areas near high voltage power line, this research measured MF levels at 120 sites near high voltage transmission lines in Busan region, Gwangju region, Daegu region and Changwon region from July to December, 2005, and compared and analyzed the efficiencies by measuring and applying the MF emission levels of underground cables and high voltage transmission line. As a result of the investigation of the MF exposure level by the building usages, the average MF level of 17 locations of schools was 2.44~2.45mG; that of 10 locations of hospitals 6.21~12.39mG; that of 76 locations of apartments 2.55~2.98mG; and that of kindergartens and infant houses 3.32~4.21mG. As an analysis result of MF exposure level by the separated distance, the level at the right below was 5.15~8.72mG, that within 30m 3.10~3.32mG, that within 50m 2.45~2.38mG, and that within 100m 0.71~0.93mG. In order to check the difference of MF levels by the actual distance from high voltage transmission line within same building, the evaluation of the height of each floor and the MF level has shown that the MF levels were high in the order of roof, 4th floor, 3rd floor, 2nd floor and 1st floor. Comparison of MF emission intensity of underground cable and high voltage transmission line, the results has shown that underground cable has 86-94% of reduction ratio in MF reduction compared to high voltage transmission line, demonstrating higher efficiency.

Abstract

In order to evaluate the magnetic field(MF) exposure level in residential areas near high voltage power line, this research measured MF levels at 120 sites near high voltage transmission lines in Busan region, Gwangju region, Daegu region and Changwon region from July to December, 2005, and compared and analyzed the efficiencies by measuring and applying the MF emission levels of underground cables and high voltage transmission line. As a result of the investigation of the MF exposure level by the building usages, the average MF level of 17 locations of schools was 2.44~2.45mG; that of 10 locations of hospitals 6.21~12.39mG; that of 76 locations of apartments 2.55~2.98mG; and that of kindergartens and infant houses 3.32~4.21mG. As an analysis result of MF exposure level by the separated distance, the level at the right below was 5.15~8.72mG, that within 30m 3.10~3.32mG, that within 50m 2.45~2.38mG, and that within 100m 0.71~0.93mG. In order to check the difference of MF levels by the actual distance from high voltage transmission line within same building, the evaluation of the height of each floor and the MF level has shown that the MF levels were high in the order of roof, 4th floor, 3rd floor, 2nd floor and 1st floor. Comparison of MF emission intensity of underground cable and high voltage transmission line, the results has shown that underground cable has 86-94% of reduction ratio in MF reduction compared to high voltage transmission line, demonstrating higher efficiency.

참고문헌 (17)

  1. Wertheimer, N., "Electrical wiring configurations and childhood cancer", American Journal of Epidemiol, 128, pp.21~38 (1998)
  2. NIESH - National Institute of Environmental Health Sciences, "EMF RAPID Program" (2002), National Institute of Health
  3. NIESH - National Institute of Environmental Health Sciences, "Assessment of Health Effects from Exposure to Power-line Frequency Electric and Magnetic Fields" (1998), National Institute of Healt
  4. WHO - World Health Organization., "Framework for Developing Health-based EMF Standards" (2006), World Health Organization
  5. Kim, Y. S., "Assessment of melatonin levels in human volunteers exposed to electromagnetic fields (EMFs)", Korean Society of Environmental Health, 23(3), pp.130~135 (1997)
  6. Kim, Y. S., "Measurement and personal exposure assessment of extremely low frequency(ELF) Electromagnetic Fields(EMF)", Korean Society of Environmental Health, 23(1), pp.55~61 (1997)
  7. 김윤신, "다양한 노출 매트릭스를 통한 송전선로 주변과 비 주변 거주 초등학교 학생의 극저주파 자기장 노출량 평가에 관한 연구", 한국산업위생학회지, 16(4), pp.334~345 (2006), 한국산업위생학회
  8. Cho, Y. S., "Relationship between urinary melatonin levels and extremely low frequency magnetic fields for the selected primary schoolchildren living nearby and away from overhead transmission power line", Korean Society of Environmental Health, 30(3), pp.191~206 (2004)
  9. 김윤신, "미세 환경 별 전자장 노출 특성", 한국실내환경학회지, 2(1), pp.1~11 (2005), 한국실내환경학회
  10. 전재경, "전자파의 법적규제-송전선로 분쟁을 중심으로", pp.28~52 (1996), 한국법제연구원
  11. 전인수, "고압선로 환경영향평가의 자기장 노출범위설정에 관한 연구", 환경영향평가, 13(5), pp.243~250 (2004), 한국환경영향평가학회
  12. 신동천., "전자파 인체권고기준 설정을 위한 조사연구" (1997), 환경부
  13. National Council on Radiation and Protection and Measurements, "NCRP Scientific Committee 89-3 on Extremely Low Frequency Electric and Magnetic Fields", ~ (1995)
  14. Neu Grenz-und Vorsogerwert und sie hewegen sich doch,Elektrosmog-report, "M. Karus", ~ (2002)
  15. A Project of California Department of Health Service and Public Health Institute Califionia, "Electric and Magnetic Fields Program", ~ (2000)
  16. 홍승철, "60Hz 고압 송전선로의 자기장 발생범위에 대한 GIS 적용 방안에 대한 연구", 환경영향평가, 15(4), pp.271~277 (2006), 한국환경영향평가학회
  17. Savits, D. A., "Case control study of childhood cancer and exposure to 60 Hz magnetic fields", American Journal of Epidemiology, 128, pp.21~38 (1998)

이 간행물의 다른 논문 (14건)