Large enclosure means a space of high ceiling and large floor. Designing the heating system, manythermal conditions exist, such as thermal comfort, IAQ, heating load and energy efficiency etc. Theprediction of the temperature distribution is carried out according to some of the diffuser angle. Thesimulation conditions are 7 m high diffuser, 4/2 inlet/outlet diffusers, 39 °C discharge air temperature,and 6 m/s exit velocity. The results show that 45° diffuser provides an optimal thermal environment, andthe reason is that the temperature is closed to the designed temperature 22 °C at 1.18m elevation plane. As the diffuser angle is decreased, the temperature of the upper region is increased for the thermalbuoyancy effect. And the asymmetry of the temperature distribution is increased.

Abstract

Large enclosure means a space of high ceiling and large floor. Designing the heating system, manythermal conditions exist, such as thermal comfort, IAQ, heating load and energy efficiency etc. Theprediction of the temperature distribution is carried out according to some of the diffuser angle. Thesimulation conditions are 7 m high diffuser, 4/2 inlet/outlet diffusers, 39 °C discharge air temperature,and 6 m/s exit velocity. The results show that 45° diffuser provides an optimal thermal environment, andthe reason is that the temperature is closed to the designed temperature 22 °C at 1.18m elevation plane. As the diffuser angle is decreased, the temperature of the upper region is increased for the thermalbuoyancy effect. And the asymmetry of the temperature distribution is increased.

참고문헌 (6)

  1. J. Y. Son, "A Prediction Technology for Temperature &Airflow Distribution in Large Enclosure", The Society of Air-conditioning & Refrigerating Engineers of Korea, 30(4), pp.12~ (2001)
  2. A Technical Research Report for Optimization of Energy-efficiency Building Equipment Design and Management System, , Ministry of Construction &Transportation, 14~ (2005)
  3. J. Y. Park, "Evaluation for Thermal Environment of Dome Stadium with Various Diffusion Angles of Nozzles", The Society of Air-conditioning & Refri- gerating Engineers of Korea, 102~ (2004)
  4. 이찬규, "창호특성 변화에 따른 농어촌 주택 표준모델의 건물에너지요구량 분석", 한국기계기술학회지, 14(6), pp.51~56 (2012), 한국기계기술학회
  5. B. T. Suh, "A Balancing Study on the Amount of Heating Load Between Outside units and Inside in an Apartment House", Jou. of Korean Soc. of Mechanical Technology, 2(2), pp.104~ (2000)
  6. The Analysis of Temperature and Airflow Distribution for Energy Conservation in Large Enclosure, , Ministry of Commerce, Industry and Energy, 26~120, pp.1997-E-BD02-P-24 (2000)