We developed a low-cost automatic diagnosis system for water quality in cooling towers to measure the concentrations of key ingredients such as Ca2+, Cl-, PO43-, and Fe2+. Ca2+, and Cl- are the main factors that cause the generation of scale, corrosion, and sludge in water pipes. PO43- prevents corrosion, sludge and scale by inhibiting the ions (i.e., Ca2+, Cl-) from sticking to the pipes. Fe2+ is an indicator of pipe corrosion. The proposed system consists of a microprocessor, a specimen container and heater, a precision pump, relays and valves, LED optical sources, and photo detectors. It automatically collects water samples and carries out pretreatment for determining the concentration of each chemical, and then estimates the concentration of each ion using low-cost LED optical sources and detectors. Experimental results showed that the accuracy of the proposed system is sufficiently high for water quality diagnosis and management of cooling towers, demonstrating the possibility of the proposed system's wide usage in real environments.

Abstract

We developed a low-cost automatic diagnosis system for water quality in cooling towers to measure the concentrations of key ingredients such as Ca2+, Cl-, PO43-, and Fe2+. Ca2+, and Cl- are the main factors that cause the generation of scale, corrosion, and sludge in water pipes. PO43- prevents corrosion, sludge and scale by inhibiting the ions (i.e., Ca2+, Cl-) from sticking to the pipes. Fe2+ is an indicator of pipe corrosion. The proposed system consists of a microprocessor, a specimen container and heater, a precision pump, relays and valves, LED optical sources, and photo detectors. It automatically collects water samples and carries out pretreatment for determining the concentration of each chemical, and then estimates the concentration of each ion using low-cost LED optical sources and detectors. Experimental results showed that the accuracy of the proposed system is sufficiently high for water quality diagnosis and management of cooling towers, demonstrating the possibility of the proposed system's wide usage in real environments.

참고문헌 (17)

  1. 이기건, "냉각탑 수질관리를 위한 자동화 시스템 개발", 제어.로봇.시스템학회 논문지, 14(1), pp.36~41 (2008), 제어·로봇·시스템학회
  2. 정영도, "pH Measurements with a Microcantilever Array-Based Biosensor System", 센서학회지, 21(3), pp.186~191 (2012), 한국센서학회[DOI]
  3. S. S. Zumdahl, "Chemistry", pp.129~179 (2007), Houghton Mifflin
  4. S. G. Hong, "Development of a multi-channel detector for capillary electrophoresis system", Anal. Sci. & Tech., 11(2), pp.96~104 (1998)
  5. D. C. Harris, "Quantitative chemical analysis, 7th edition", pp.228~249 (2007), W.H. Freeman & Company
  6. S. Ann, "Environmental chemistry", pp.330~435 (2001), DongHwa Technology Publishing
  7. D. G. Jones, "Photodiode array detectors in UV-VIS spectroscopy:part II", Anal. Chem, 57(11), pp.1207A~1214A (1985)
  8. R. S. Berns, "Billmeyer and Saltzman's Principles of color technology, 3rd edition", pp.67~109 (2000), Wiley
  9. D. A. Skoog, "Principles of Instrumental Analysis", pp.2007, Brooks
  10. F. Rouessac, "Chemical Analysis: Modern Instrumentation Methods and Techniques", pp.167~206 (2007), WILEY
  11. R. Pallas-Areny, "Sensors and Signal Conditioning", pp.277~321 (2001), John Wiley & Sons Inc
  12. M. E. V. Valkenburg, "Analog Filter Design", pp.157~213 (1982), CBS College Publishing

관련 논문AI추천

이 간행물의 다른 논문 (11건)