본문 바로가기
KERD
논문KCI 등재

중환자실 병상주변공간의 면적과 간격에 관한 연구

A Study on the Area and Clearances around Patient Bed Space in Intensive Care Unit

0

조회

0

다운로드

4

인용

0

참고문헌

키워드

주제분류건축공학

초록

Purpose: This study tries to propose the dimensions and area related to patient bed and surroundings in ICU considering nurses’ observation and medical care. Methods: Literature survey, 11 Case studies, some Interviews with nurses and measuring of medical equipments’ dimension in ICU have been mobilized in order to deepen the ICU bed area standards. Results: 0.3m clearance between head wall and patient bed is necessary for emergency cases. The minimum distance at the foot of the bed should not be less than 0.9m for EMR cart and medical tray. The clear floor area of one bed and surroundings in open ward is 10.2㎡(3m×3.4m). In a single-bed patient room, the minimum clear floor area is 16.0㎡(4m×4m). Considering the control of cross infection in ICU, Single bed patient room is recommended. Implications: The result of this study can be applied to the design of ICU and legislation of ICU standard.

Abstract

Purpose: This study tries to propose the dimensions and area related to patient bed and surroundings in ICU considering nurses’ observation and medical care. Methods: Literature survey, 11 Case studies, some Interviews with nurses and measuring of medical equipments’ dimension in ICU have been mobilized in order to deepen the ICU bed area standards. Results: 0.3m clearance between head wall and patient bed is necessary for emergency cases. The minimum distance at the foot of the bed should not be less than 0.9m for EMR cart and medical tray. The clear floor area of one bed and surroundings in open ward is 10.2㎡(3m×3.4m). In a single-bed patient room, the minimum clear floor area is 16.0㎡(4m×4m). Considering the control of cross infection in ICU, Single bed patient room is recommended. Implications: The result of this study can be applied to the design of ICU and legislation of ICU standard.

참고문헌 (16)

  1. AHIA(Australasian Health Infrastructure Alliance), "Australasian Health Facility Guidelines, part B, 360-Intensive care-General", ~ (2016)
  2. CSA (Canadian Standards Association), "CHCF: Canadian Health Care Facilities", ~ (2017)
  3. DH, "HBN 04-02, In-patient Health Building Note 04-02: Critical care unit", ~ (2013)
  4. FGI (The Facility Guidelines Institute), "Guidelines for Design and Construction of Hospitals and Outpatient Facilities" (2018)
  5. Architectural Guidelines for the Design of Healthcare Facilities, "Korea Institute of Healthcare Architecture", ~ (2018)
  6. 의료시설 건축설계 가이드라인 구축 연구, "국립중앙의료원", ~ (2018)
  7. 김상복, "병원감염 방지를 위한 중환자부의 건축계획적 연구", 의료·복지 건축, 10(2), pp.29~37 (2004), 한국의료복지건축학회
  8. 보건복지부, "의료법시행규칙", ~ (2017)
  9. 보건복지부, "2주기 급성기병원 인증조사기준", ~ (2016)
  10. 의료기관 시설기준 개선방안 연구, "연세대학교의료법윤리학연구원", ~ (2013)
  11. 윤우용, "중환자부 시설기준 수립을 위한 가이드라인 조사‧분석연구 - 미국, 영국, 호주 사례를 중심으로", 의료·복지 건축, 21(4), pp.17~25 (2015), 한국의료복지건축학회[DOI]
  12. 윤우용, "지역거점공공의료원 중환자부 공간구성 및 면적계획에 관한 연구", 의료·복지 건축, 23(2), pp.47~61 (2017), 한국의료복지건축학회[DOI]
  13. 윤형진, "중환자실 시설기준 작성을 위한 기본시설 수준 설정 연구 - 국내·외 시설기준 및 국내 종합병원 병상규모 별 시설 현황분석을 기초로 하여", 의료·복지 건축, 23(3), pp.47~56 (2017), 한국의료복지건축학회[DOI]
  14. 이현진, "2015년 메르스 사태 이후 신축된 종합병원 병동부의 공간구성 특징 및 입원실 세부시설기준에 관한 연구", 의료·복지 건축, 25(2), pp.27~35 (2019), 한국의료복지건축학회[DOI]
  15. 이현진, "병원 감염관리를 위한 중환자부 공간계획에 관한 연구", 의료·복지 건축, 22(4), pp.87~95 (2016), 한국의료복지건축학회[DOI]
  16. 질병관리본부, "중환자실에서의 감염관리 표준지침개발", ~ (2010)

관련 논문AI추천

이 간행물의 다른 논문 (9건)