디지털 트윈 기반의 BEMS 적용을 통한 건물에너지 효율화 방법
Building Energy Efficiency through the Application of Digital Twin-based BEMS
0
조회
0
다운로드
0
인용
0
참고문헌
키워드
초록
Building energy management systems (BEMS) are widely used to improve building energy efficiency. However, beyond simple monitoring and management, there are still limitations to implementing specific methods for energy savings and efficiency improvements during the operational phase. Simultaneously, the concept of a digital twin (DT) has been actively researched as a concept for the interaction of data and operational information between real buildings and virtual models. By integrating the DT concept into the BEMS, smooth communication between real buildings and virtual models is possible. A virtual model is defined as a mathematical model that describes physical behavior during the operational phases of a real building. This model can provide building energy efficiency methods based on real building data and the physical behavior of the building. Therefore, this study proposes a DT-based BEMS (DT-BEMS). A DT-BEMS consists of predicted mean vote (PMV) virtual sensors, energy sub-metering virtual sensors, and Holistic Operational Signature (HOS) analysis methods. Utilizing data from the BEMS, PMV virtual sensors obtain the PMV in real residential areas. After applying the virtual sensors, the HOS categorizes the operational states and offers energy optimization information. In this study, a DT-BEMS environment was developed for an office building. Thus, an organic process was realized in which real building data were transmitted through virtual models to provide energy efficiency information back to the target building.
Abstract
Building energy management systems (BEMS) are widely used to improve building energy efficiency. However, beyond simple monitoring and management, there are still limitations to implementing specific methods for energy savings and efficiency improvements during the operational phase. Simultaneously, the concept of a digital twin (DT) has been actively researched as a concept for the interaction of data and operational information between real buildings and virtual models. By integrating the DT concept into the BEMS, smooth communication between real buildings and virtual models is possible. A virtual model is defined as a mathematical model that describes physical behavior during the operational phases of a real building. This model can provide building energy efficiency methods based on real building data and the physical behavior of the building. Therefore, this study proposes a DT-based BEMS (DT-BEMS). A DT-BEMS consists of predicted mean vote (PMV) virtual sensors, energy sub-metering virtual sensors, and Holistic Operational Signature (HOS) analysis methods. Utilizing data from the BEMS, PMV virtual sensors obtain the PMV in real residential areas. After applying the virtual sensors, the HOS categorizes the operational states and offers energy optimization information. In this study, a DT-BEMS environment was developed for an office building. Thus, an organic process was realized in which real building data were transmitted through virtual models to provide energy efficiency information back to the target building.
참고문헌 (11)
- Building Energy Management Systems - Part 2: Selection of Control Points, Data Management, and Energy Savings Calculation, "Industrial Standardization Council", ~ (2021)
- Regulations on Promotion of Rationalization of Energy Use in Public Institutions, No. 2024-46, "Ministry of Trade, Industry and Energy", ~ (2024)
- Macchi, M., "Exploring the Role of Digital Twin for Asset Lifecycle Management", IFAC-PapersOnLine, 51, pp.790~795 (2018)
- Yoon, S., "Building Digital Twinning: Data, Information, and Models", Journal of Building Engineering, 76, pp.107021~ (2023)[DOI]
- AlBalkhy, W., "Digital Twins in the Built Environment: Definition, Applications, and Challenges", Automation in Construction, 162, pp.105368~ (2024)[DOI]
- "BrickSchema, Home"[URL]
- Fanger, P. O., "Thermal Comfort, Analysis and Applications in Environmental Engineering" (1970), Danish Technical Press
- Kim, J., "Virtual PMV Sensor towards Smart Thermostats : Comparison of Modeling Approaches Using Intrusive Data", Energy and Buildings, 301, pp.113695~ (2023)[DOI]
- ISO, "ISO 7730: Ergonomics of the Thermal Environment-Analytical Determination and Interpretation of Thermal Comfort Using Calculation of the PMV and PPD Indices and Local Comfort Criteria", ~ (2005)
- Hong, Y., "Holistic Operational Signatures for an Energy-Efficient District Heating Substation in Buildings", Energy, 250, pp.123798~ (2022)[DOI]
- Hong, Y., "Operational Signature-Based Symbolic Hierarchical Clustering for Building Energy, Operation, and Efficiency Towards Carbon Neutrality", Energy, 265, pp.126276~ (2023)[DOI]