본문 바로가기
KERD
논문KCI 등재

부산 지역 사무실 실내 공기질 조사

Study of Indoor Air Quality from the Several Offices in Busan Area

1

조회

0

다운로드

5

인용

0

참고문헌

초록

Abstract

The indoor air quality was investigated from the six offices in Busan Metropolitan City. The indoor concentrations of PM10, CO2, CO and HCHO were determined and outdoor levels of CO and PM10 were compared with those of indoor levels. Three offices were located in the industrial area and the others were in the commercial area. The concentration ranges (means and standards deviations) of PM10, CO2, CO and HCHO were 140.7-67.4 (109.0 ± 27.0) μg/m3, 592.0 - 1,060.0 (776.4 ± 169.1) ppm, 1.4 - 3.1 (2.0 ± 0.8) ppm, and 8.3 - 21.1 (16.2 ± 5.1) μg/m3, respectively. The pollutant concentrations were about 1.5 times higher in the industrial area than those of in the commercial area

참고문헌 (8)

  1. 노영만, "제목없음", 한국산업위생학회지, 14(3), pp.270~282 (2004)
  2. 이철민, "제목없음", 한국산업위생학회지, 14(3), pp.251~263 (2004)
  3. "산업안전 보건법 산업보건에 관한 규칙(2003. 7. 12.)", ~ (2003), 제4장 제49조 별표 4
  4. M. Gerin, "Database(www2a.cdc.gov", nioshtic-2), 1991, pp.6(6), 495~501[DOI]
  5. "제목없음" (2009)[URL]
  6. "작업환경측정·분석방법지침(KOSHA CODE A-1-2004)", 한국산업안전공단, 355~366, No. A-1- 067. 알데히드류I, II.
  7. "Thermal Environmental Conditions for Human Occupancy Atlanta.", ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning, INC., ~, Standard 55-1992,
  8. "다중이용시설 등의 실내 공기질관리법’(일부개정 2003.5.31 법률 제7562호) 동 시행규칙 ‘다중이용시설 등의 실내 공기질관리법 시행규칙’(일부개정 2006.3.13 환경부령 제201호) 제3조 별표 2.", ~

이 간행물의 다른 논문 (9건)